Siemens SED2 Specifications Page 45

  • Download
  • Add to my manuals
  • Print
  • Page
    / 132
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 44
Electrical Installation
Siemens Building Technologies, Inc. 35
Table 6. Cable Cross-Sections for Input Voltage Range
3Ø AC 380V through 480V.
Input Power Cable Motor Cable
Maximum
Output
rating
kW (hp)
Minimum
Cross-
Section
AWG (mm
2
)
Maximum
Cross-
Section
AWG (mm
2
)
Minimum
Cross-
Section
AWG (mm
2
)
Maximum
Cross-
Section
AWG (mm
2
)
0.37 (.50)
17 (1) 13 (2.5) 17 (1) 13 (2.5)
0.55 (.75)
17 (1) 13 (2.5) 17 (1) 13 (2.5)
0.75 (1.0)
17 (1) 13 (2.5) 17 (1) 13 (2.5)
1.1 (1.5) 17 (1) 13 (2.5) 17 (1) 13 (2.5)
1.5 (2.0) 17 (1) 13 (2.5) 17 (1) 13 (2.5)
2.2 (3.0) 17 (1) 9 (6) 17 (1) 9 (6)
3 (4.0) 17 (1) 9 (6) 17 (1) 9 (6)
4 (5.0) 17 (1) 9 (6) 17 (1) 9 (6)
5.5 (7.5) 13 (2.5) 7 (10) 13 (2.5) 7 (10)
7.5 (10) 11 (4) 7 (10) 11 (4) 7 (10)
11 (15) 9 (6) 7 (10) 9 (6) 7 (10)
15 (20) 7 (10) 2 (35) 7 (10) 2 (35)
18.5 (25) 7 (10) 2 (35) 7 (10) 2 (35)
22 (30) 5 (16) 2 (35) 5 (16) 2 (35)
30 (40) 3 (25) 2 (35) 3 (25) 2 (35)
37 (50) 3 (25) 2 (35) 2 (35) 2 (35)
45 (60) 2 (35) -5 (150) 2 (35) -5 (150)
55 (75) -2 (70) -5 (150) -2 (70) -5 (150)
75 (100) -2 (70) -5 (150) -3 (95) -5 (150)
90 (125) -2 (70) -5 (150) -3 (95) -5 (150)