Appendix B: SED2 Point Cross-Reference
Siemens Building Technologies, Inc. 113
Table 10. SBT P1 Point Cross Reference to SED2.
Point
No.
Point
Type
Descriptor
Factory
Default
(SI
Units)
Eng.
Units
(SI
Units)
On Text
Off
Text
SED2
Reference
68 LAI LOW PASS 0 –
71 LDI DIGITAL IN 1 0 – ON OFF r0722 bit 0
72 LDI DIGITAL IN 2 0 – ON OFF r0722 bit 1
73 LDI DIGITAL IN 3 0 – ON OFF r0722 bit 2
74 LDI DIGITAL IN 4 0 – ON OFF r0722 bit 3
75 LDI DIGITAL IN 5 0 – ON OFF r0722 bit 4
76 LDI DIGITAL IN 6 0 – ON OFF r0722 bit 5
80 LAO WDOG TIME 0 –
83 LAI INVERTER VER 0 – r0018
84 LAI DRIVE MODEL 0 –
90 LAI LAST FAULT 0 – r0947(0)
91 LAI 1st FAULT 0 – r0947(1)
92 LAI 2nd FAULT 0 – r0947(2)
93 LAI 3rd FAULT 0 – r0947(3)
94 LDI OK FAULT 0 – FAULT OK r0052 bit 3
95 LDO FAULT ACK 0 – ON OFF r0054 bit 7
96 LDI WARNING 0 – WARN OK r0052 bit 7
97 LAI
LAST WARNING
0 –
r2110 (0)
99 LAO
ERROR STATUS
0 –