Technical data
6.2 Electrical Data
Power Modules PM240
Hardware Installation Manual, 2006-04-04, A5E00807525B AA
6-7
Braking resistor data
Table 6-5 Data for braking resistors
I
DC_max
for Frame size Rated Voltage V
DC_max
A B C D E F
400 V 820 V … 840
V
2.15 A
(390 Ω)
5.25 A
(160 Ω)
15 A
(56 Ω)
30.4 A
(27 Ω)
54.7 A
(15 Ω)
100.0 A
(8.2 Ω)
Power Module PM240 Specifications
Caution
High Overload (HO) and Light Overload (LO) input currents
The input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 1 % referred to the rated SINAMICS G120 Power Module power and a rated line
supply voltage of 400 V without line a commutating reactor. If a line commutating reactor is
used, the specified values are reduced by between 70 % and 80 %.
Notice
UL certified Fuses must be used
In order that the system is in compliance with UL, UL certified fuses, circiut-breaker or self
protected combination motorcontroller must be used.