Power Modules PM240
Hardware Installation Manual, 2006-04-04, A5E00807525B AA
6-1
Technical data
6
6.1 Mechanical Data
Distances to other equipment
When mounting the SINAMICS G120 Power Modules one above the other or side by side,
the specified environmental conditions must not be exceeded. Independent of this, these
minimum distances of the SINAMICS G120 Power Modules must be observed:
Table 6-1 Distances to other equipment
A B C D E F
Frame
Size
mm inch mm inch mm inch mm inch mm inch mm inch
Side
by
Side
30 1.18 40 1.57 50 1.96 0 0 0 0 0 0
Above
and
Below
100 3.93 100 3.93 125 4.92 300 11.81 300 11.81 350 13.77
Ambient operating conditions
Temperature
The normal operating temperature range of the SINAMICS G120 Power Module is as
follows:
0 °C … + 50 °C (32 °F … 122 °F) High Overload (HO)
0 °C … + 40 °C (32 °F … 104 °F) Light Overload (LO).
The ambient operating temperature is shown diagramatically in the figure below.