Installing/Mounting
4.2 Electrical Installation
Power Modules PM240
Hardware Installation Manual, 2006-04-04, A5E00807525B AA
4-11
Connecting example
The figure below shows the recommended power and motor connections when installing a
SINAMICS G120 inverter.
/
/
/
3(
3(
/
3(
/
/
8
9
:
6FKPHO]
VLFKHUXQJ
6FK¾W]
2SWLRQDOHU
)LOWHU
2SWLRQDOH
1HW]GURVVHO
6,1$0,&6* 0RWRU
'UHKVWURP
Figure 4-10 Motor and power connections
Operation with ungrounded (IT) supplies
IT supplies are fully isolated from the protective earth system, usually by an isolating
transformer. It should be noted, however, that a protective earth is still provided.
Warning
SINAMICS G120 Power Modules with built-in filters or external filters must not be used with
IT supplies.
SINAMICS G120 Power Modules connected to IT supplies must have their internal 'Y'
capacitors disconnected (see below). If the SINAMICS G120 Power Module connected to an
IT supply is required to remain operational if an input or output phase is connected to
ground, then an output choke must be fitted to prevent tripping.
Operation of the SINAMICS G120 Power Modules without a protective earth is not permitted
under any circumstances.
For more information on chokes, please refer to the product catalog.
Operation with Residual Current Devices (RCD)
If an RCD (also referred to as an ELCB or a RCCB) is fitted, the SINAMICS G120 Power
Module will operate without nuisance tripping provided that:
A type B RCD is used.
The trip limit of the RCD is 300 mA.
The neutral of the supply is grounded.
Only one SINAMICS G120 power module is supplied from each RCD.
The output cables are less than 50 m (164 ft) screened or 100 m (328 ft) unscreened.
Avoiding Electromagnetic Interference (EMI)
The inverters are designed to operate in an industrial environment where a high level of EMI
can be expected. Most installations do not give problems. However, it is good engineering