Installing/Mounting
4.2 Electrical Installation
Power Modules PM240
4-16 Hardware Installation Manual, 2006-04-04, A5E00807525B AA
87 Hz characteristic
When a motor with a delta circuit configuration (e.g. V
N∆
, motor = 230 V) is fed from a
frequency inverter, where the rated voltage corresponds to the star circuit configuration (e.g.
400 V frequency inverter), then it is important to proceed as follows and observe the
following:
• The motor must have the appropriate voltage strength.
• Above the rated motor frequency, the iron losses in the motor increase over-
proportionally. This is the reason that above this frequency, the thermal motor torque
should be reduced.
• For the quick commissioning, the rating plate data for the delta circuit configuration
should be entered or the rating plate must be appropriately converted.
• The inverter must be designed for the higher current (delta circuit configuration).
• The 87 Hz characteristic is independent of the control type and can therefore be used
both for V/f control as well as for closed-loop vector control.
• When using the 87 Hz characteristic, the mechanical motor limits must be taken into
account.
For the 87 Hz characteristic, the ratio between the voltage and frequency (V/f characteristic)
remain constant. This is the reason that the following relationships apply:
P
U
U
P
NΔ
NΔ
N1
N1
⋅=
f
U
U
f
NΔ
NΔ
N1
N1
⋅=
()
n
ff
n
Δ
NΔN1
N1
p
min
s
60
+−
⎥
⎦
⎤
⎢
⎣
⎡
=
f
f
N1
f
N∆
U
U
N∆
U
N1
(400 V)
(230 V)
(50 Hz) (87 Hz)
3 /HLVWXQJ
I )UHTXHQ]
Q 'UHK]DKO
S 3ROSDDU1U
Figure 4-14 V/f characteristic
Table 4-3 Example 1LA7060-4AB10
Delta circuit
configuration
87 Hz
characteristic
Star circuit
configuration
P0304 Rated motor voltage 230 V 400 V 400 V
P0305 Rated motor current 0.73 A 0.73 A 0.42 A
P0307 Rated motor power 120 W 207 W 120 W
P0308 cos φ 0.75 0.75 0.75
P0310 Rated motor frequency 50 Hz 87 Hz 50 Hz
P0311 Rated motor speed 1350 RPM 2460 RPM 1350 RPM
P0314 Motor pole pairs 2 2 2
Contrary to the OP, the STARTER commissioning (start-up) program offers a mask-
orientated quick commissioning. On the other hand, the OP offers, in conjunction with the
inverter, parameter-orientated quick commissioning.