Installing/Mounting
4.2 Electrical Installation
Power Modules PM240
4-16 Hardware Installation Manual, 2006-04-04, A5E00807525B AA
87 Hz characteristic
When a motor with a delta circuit configuration (e.g. V
N∆
, motor = 230 V) is fed from a
frequency inverter, where the rated voltage corresponds to the star circuit configuration (e.g.
400 V frequency inverter), then it is important to proceed as follows and observe the
following:
The motor must have the appropriate voltage strength.
Above the rated motor frequency, the iron losses in the motor increase over-
proportionally. This is the reason that above this frequency, the thermal motor torque
should be reduced.
For the quick commissioning, the rating plate data for the delta circuit configuration
should be entered or the rating plate must be appropriately converted.
The inverter must be designed for the higher current (delta circuit configuration).
The 87 Hz characteristic is independent of the control type and can therefore be used
both for V/f control as well as for closed-loop vector control.
When using the 87 Hz characteristic, the mechanical motor limits must be taken into
account.
For the 87 Hz characteristic, the ratio between the voltage and frequency (V/f characteristic)
remain constant. This is the reason that the following relationships apply:
P
U
U
P
N1
N1
=
f
U
U
f
N1
N1
=
()
n
ff
n
Δ
N1
N1
p
min
s
60
+
=
f
f
N1
f
N
U
U
N
U
N1
(400 V)
(230 V)
(50 Hz) (87 Hz)
3 /HLVWXQJ
I )UHTXHQ]
Q 'UHK]DKO
S 3ROSDDU1U
Figure 4-14 V/f characteristic
Table 4-3 Example 1LA7060-4AB10
Delta circuit
configuration
87 Hz
characteristic
Star circuit
configuration
P0304 Rated motor voltage 230 V 400 V 400 V
P0305 Rated motor current 0.73 A 0.73 A 0.42 A
P0307 Rated motor power 120 W 207 W 120 W
P0308 cos φ 0.75 0.75 0.75
P0310 Rated motor frequency 50 Hz 87 Hz 50 Hz
P0311 Rated motor speed 1350 RPM 2460 RPM 1350 RPM
P0314 Motor pole pairs 2 2 2
Contrary to the OP, the STARTER commissioning (start-up) program offers a mask-
orientated quick commissioning. On the other hand, the OP offers, in conjunction with the
inverter, parameter-orientated quick commissioning.