2.1 Supplementary electrical conditions
2-24
Copyright © Siemens AG 2006
SINUMERIK 810D Equipment Manual Configuration CCU (PHC) – 03/2006 Edition
2.1.1 Power supply
!
Warning
The DC power supply is always referenced to ground and must be
generated by a safety transformer.
Final user interfaces are powered via a DC power supply with protective
separation per EN 61800-5-1.
In the case of supply cables > 10 m, protective elements must be fitted at
the device input in order to protect against lightning (surge voltage).
The DC power supply must be connected to the ground/shield of the NC for
EMC and/or functional reasons. For EMC reasons, this connection should
only be made at one point. As a rule, the connection is provided as
standard in the S7-300 I/Os. If this is not the case in exceptional circum-
stances, the ground connection should be made to the grounding rail of the
NC cabinet; also refer to /EMC/ EMC Configuring Guidelines.
Table 2-1 Requirements of the DC supply
Rated voltage In accordance with EN 61131-2
Voltage range (average value)
Voltage ripple peak-to-peak
Ramp-up time at power-on
24 V DC
20.4 V DC to 28.8 V DC
5 % (unfiltered 6-pulse rectification)
Any
Non-cyclic overvoltages
Duration
Restoration time
Events per hour
35 V
500 ms
50 s
10
Transient voltage interruptions
Outage time
Restoration time
Events per hour
3 ms
10 s
10
The EP and CP points for the power modules only apply in conjunction with the
SINUMERIK 810D (axis expansion). The EP and CP points from Catalog NC 60
apply when SIMODRIVE 611D modules with control plug-in units are used.
Demands on DC
power supplies
Configuration
810D power
consumption
2
Connection Conditions