ISGS Settings Worksheet for Date: Set A
Siemens Energy & Automation, Inc. S-5
A2200 Overvoltage (59)
A2201 Function 59 Enabled Disabled
A2202 Curve 59 Inverse
Moderately
Inverse
Very Inverse Definite Inverse
A2203
Pickup Source Voltage 59
(if VT mode is (L-N)
Line-to-Line Line-to-Neutral
A2204 Pickup 59 130 V Range: 60-250 V (0.1 V steps) V
A2205 Time Delay 59 (Definite) 0.10 s
Range: 0-60 s (0.01 s steps),
or
∞
s
A2206 Time Dial 59 (Inverse) 0.1 Range: 0.1-9.9 (0.1 steps)
2210 Freeze Waveform 1 59 on Pickup on Trip None
2211 Freeze Waveform 2 59 on Pickup on Trip None
A2300 Undervoltage (27)
A2301 Function 27 Enabled Disabled
A2302 Curve 27 Inverse
Moderately
Inverse
Very Inverse Definite Inverse
A2303
PU Source V 27
(if VT mode is (L-N)
Line-to-Line Line-to-Neutral
A2304 Pickup 27 50 V Range: 40-230 V (0.1 V steps) V
A2305 Time Delay 27 (Definite) 0.10 s
Range: 0-60 s (0.01 s steps),
or
∞
s
A2306 Time Dial 27 (Inverse) 0.1 Range: 0.1-9.9 (0.1 steps)
2310 Freeze Waveform 1 27 on Pickup on Trip None
2311 Freeze Waveform 2 27 on Pickup on Trip None