Control & Communications
32 Siemens Energy & Automation, Inc.
Matrixing Procedure
The following steps provide a detailed description on how to
matrix the ISGS relay manually using the front panel LCD and
keypad. Before matrixing the relay, ensure that power is
applied to the relay which is indicated by the lit system LED
(green).
Table 6.1 Matrixing Procedure
How to Matrix Inputs to Outputs
Step Description
1
Press Direct Addr key; enter block address of one of the
matrix functions (6100, 6200, or 6400) using the numeric
keypad; press Enter key.
OR
Press Direct Addr key; enter the address of the desired
parameter using the numeric keypad; press Enter key.
Skip to step 4.
A complete list of ISGS relay parameters is provided in
Appendix C.
2
Use Single Arrow keys to scroll to the desired address.
3
Press F key once; use Single Arrow keys to scroll to the
desired matrix position (001-020)
4
Press Password key; enter your level 3 password fol-
lowed by Enter key. The message PW THREE
ACCEPTED appears. Press Enter key again to return to
the screen displayed last before password entry.
For password levels, proper password entry, and display
messages, refer to Section 3.3.
5
The display cursor located next to the address is blinking
(otherwise repeat step 4). Press No key until the desired
parameter option appears on display. Press Enter key to
set the displayed option.
Your settings can be undone any time while still in the
same address block by simply returning to the parameter
and assigning a new value.
Use Single Arrow keys to move to the next matrix posi-
tion to change additional parameters, or proceed to the
next step.
6
Press F key. At the blinking cursor position, the letter F is
displayed. Press Enter key. Message SAVE NEW SET-
TINGS? appears.
7
Press Yes key followed by Enter key to save settings and
reset relay to new parameters. Message NEW SET-
TINGS SAVED appears.
Press No key to abort any changes made. Message
SAVING PROCEDURE ABORTED appears.
8
Press Enter key to return to screen displayed last before
starting saving procedure.
Wisdom Software
While the ISGS relay can be matrixed manually using the
keypad and LCD, Wisdom configuring and analysis software
allows faster and easier configuration by connecting a PC
installed to either data port. For data port connections refer
to Section 2.5.1. All binary inputs, binary outputs, and the
trip contacts can be simply checked off inside the configura-
tion window of protective and other functions. Refer to
Chapter 8 for more description of how this can be done with
Wisdom software.
6
isv3o_1.bk : isv3oc&c.frm Page 32 Wednesday, August 7, 1996 10:51 AM