Siemens ISGS SG8158-00 User Manual Page 45

  • Download
  • Add to my manuals
  • Print
  • Page
    / 121
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 44
Control & Communications
Siemens Energy & Automation, Inc. 39
Figure 6.6 Current Balance Threshold
Failure of this check will cause an event Current Balance
Error. This event can activate an output contact.
The pickup value (3422) for the current balance check
depends on the secondary phase CT rating and the value is
in secondary amperes. For 5 A CTs, the value ranges from
0.5 to 5.0 A; and the value for 1 A CTs ranges from 0.1 to
1.0 A. Both values can be set in steps of 0.1 A. If one of the
three phase currents is above the preset threshold, the mon-
itoring function is activated.
The current balance factor indicates the amount of unbal-
ance tolerated before the function generates an alarm
(3424). This factor is provided to compensate for differences
between primary CTs. It ranges from 0.1 to 0.95 and can be
set in steps of 0.01.
6.11 Parameter Sets
The ISGS relay can be programmed to operate with either of
two parameter setsset A or set B. Separate parameter
sets are programmed to satisfy separate user defined condi-
tions, such as seasonal considerations or special operating
periods. For example, set A may be used for protective set-
tings used in the summertime, whereas set B might com-
prise the settings appropriate to winter, when lower ambient
temperatures could allow higher loading than in the summer.
Alternatively, set A might be configured for normal production
periods, with set B reserved for construction or periodic
shutdown periods. The choice of two separate parameter
sets prevents the need to reconfigure the relay when condi-
tions change and different parameter settings are desired.
Figure 6.2 shows the use of these parameter sets. The val-
ues in set A or B may be chosen as the active set, and are
thus put in the relays memory for easy access. The default
set includes all the factory default values and these values
are stored in long-term memory.
Figure 6.2 Parameter Set Actions
Only certain protective function parameters have two set-
tings. All A settings are grouped under parameter set A, and
all B settings are grouped under parameter set B. Each
parameter set automatically includes all the regular parame-
ters that can be programmed to only one setting at a time
7101 Parameter Set
Address Parameter Description
7101 Active Set Displays active parameter set
(A or B)
7103 Activation Activate set A or set B
7104 Copy Default to A Copy default set to set A
7105 Copy Default to B Copy default set to set B
7106 Copy A to B Copy set A to set B
7107 Copy B to A Copy set B to set A
Save
Save
Copy
Activate
Default
Set
Active
Set
Set B
Set A
6
isv3o_1.bk : isv3oc&c.frm Page 39 Wednesday, August 7, 1996 10:51 AM
Page view 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 120 121

Comments to this Manuals

No comments