4 DP Master Mode with a PROFIBUS CP in a SIMATIC S7-300
A89
S7-CPs for PROFIBUS Configuring and Commissioning
Release 09/2011
C79000G8976C18105
4.3.2 The DP States of the DP Masters
Overview
Communication between the DP master and DP slaves can be divided into four
modes:
OFFLINE
STOP
CLEAR
RUN
Each of these modes is characterized by defined actions between the DP master
and the DP slaves.
Mode Meaning Priority
1)
OFFLINE There is no communication whatsoever between the DP master
and the DP slaves. This is the initial status of the DP master.
If an assignment to a master was saved on the DP slave, this is
cleared when the slave enters the offline mode so that the DP
slave can then have parameters assigned and be configured by
other DP masters.
1
STOP
2)
There is also no communication between the DP master and DP
slaves in this mode.
If an assignment to a master was saved on the DP slave, this is
not cleared when the slave enters the stop mode so that the DP
slave cannot have parameters assigned and be configured by
other DP masters.
2
CLEAR In this mode, the master configures and assigns parameters to all
DP slaves entered in the CP database and activated. Following
this, the cyclic data exchange between the DP master and DP
slaves begins. In the CLEAR mode, the value 0H or configured
substitute values is sent to the slaves with process output or an
empty frame, in other words,. process output is deactivated.
Process inputs remain active.
3
RUN
3)
The cyclic data transfer to the DP slaves takes place in the RUN
mode. This is the productive phase. In this mode, the DP slaves
are addressed one after the other by the DP master. The call
frame contains the current output data and the corresponding
response frame contains the current input data.
4
1
If different modes are requested by the DP system (for example by the CPU or a master class 2), the mode
with the highest priority is adopted (1 = highest; 4 = lowest).
2) N
ote: With newer modules (refer to the information in the manual /2/), the STOP mode is now
the OFFLINE mode.
3) Corresponds to OPERATE in the DP standard.