7 Configuring FDL Connections / Programming the SEND/RECEIVE Interface
A164
S7-CPs for PROFIBUS Configuring and Commissioning
Release 09/2011
C79000G8976C18105
Table 7-1 , continued
Local Endpoint
Block Parameters
ID This value must be entered as a block call parameter ID in the user program to
identify the connection.
LADDR This decimal value must be entered as a block call parameter LADDR in the user
program to identify the CP (display in hexadecimal, 200
H
> 512
D
).
Connection Name (Reference) only in a multiproject
If you create a connection to a partner in another project, that has not yet been
merged with the current multiproject, you must enter a connection name as
reference. Interproject connections can then be joined up based on this reference.
As soon as the connections have been brought together, the connection name
(reference) can no longer be entered.
Routing to Distribute Load
If two or more CPs of the same type exist in a station and are connected to the
same subnet, you can select the route.
Click the “Route” button in the “General” tab to display the route dialog:
If you have configured load distribution at the local or remote end on two or more
PROFIBUS CPs, you can assign the connection to the required route via the CPs.