4 DP Master Mode with a PROFIBUS CP in a SIMATIC S7-300
A82
S7-CPs for PROFIBUS Configuring and Commissioning
Release 09/2011
C79000G8976C18105
4.1 Overview
Differences Compared with the Integrated DP Interface
When using the PROFIBUS CP, note the following differences compared with the
integrated DP interfaces in the CPU:
In the configuration:
The DP master system is created when the CP is configured and not when
the CPU is configured.
In the programming:
Reading and writing process and diagnostic data must be started using an
FC.
In addition to the process image, memory bits or data blocks can also be
used as peripheral data areas.
In the use of the variable table VAT:
Direct enabling of the process image PI is not supported since the outputs of
the peripheral I/Os are set by blocks (FCs).