33 / 44
Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en
Building Technologies Handling 2012-10-02
When the controller is used with a compressor, the minimum output on-time
(parameter P48) and off-time (parameter P49) for Y11/Y21 must be adjusted to
avoid damaging the compressor and shortening its life
Recalibrate the temperature sensor if the room temperature displayed on the
controller does not match the room temperature measured. To do this, change
parameter P05
We recommend to review the setpoints and setpoint ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
energy
5.2 Operating Instructions
See the operating instructions B3076... enclosed with the controller.
5.3 Disposal
The device is classified as waste electronic equipment in terms of the European
Directive 2002/96/EC (WEEE) and should not be disposed of as unsorted muni-
cipal waste.
The relevant national legal rules are to be adhered to. Regarding disposal, use
the systems setup for collecting electronic waste.
Observe all local and applicable laws.
Compressor-based
application
Calibrate sensor
Setpoint and range
limitation