Siemens RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation CE1P3076.en
Building Technologies Functions 2012-10-02
4.6.1 2-pipe fan coil unit
In 2-pipe applications, the controller controls a valve in heating/cooling mode with
changeover (automatic or manual), heating only mode, or cooling only mode.
Cooling only is factory set (P01=1).
The diagram below shows the control sequence for on/off (2-position) control.
Heating mode Cooling mode
½ SDH
1
0
½ SDH
w
Y
3076D01
T[°C]
Y1
Y
½ SDC
1
0
½ SDC
w
3076D02
T[°C]
Y1
T[°C] Room temperature SDH Switching differential “Heating”
w Room temperature setpoint SDC Switching differential “Cooling”
Y1 Control command “Valve” or “Compressor”
The diagram below shows the control sequence for continuous PI control.
Heating mode Cooling mode
XpH
100
0
w
Y [%]
3076D03
T[°C]
Y1
XpC
Y [%]
100
0
w
3076D04
T[°C]
Y1
T[°C] Room temperature XpH Proportional band “Heating”
w Room temperature setpoint XpC Proportional band “Cooling”
Y1 Control command “Valve”
The diagrams only show the PI thermostat’s proportional part.
For the fan sequence see section 4.8.
On/off o
utput
Heating or cooling
Control sequence
on/off output
Control sequence
modulating output
Notes: