Diagnostic T
ests and T
roubleshooting
5-5
If the Peerlink module fails one of the user
-initiated diagnostic tests
routines, the front panel indicators will light as described in the following.
LED Description
MODULE GOOD
Lights when the module passes the ROM and RAM
integrity tests.
P/C COMM GOOD
Lights when the module passes the communications
integrity tests.
TRANSMIT
Lights (with the RECEIVE LED) when Channel A
passes the integrity tests.
RECEIVE
Lights when Channel B passes the integrity tests.
When the TEST indicator begins flashing, the user
-initiated diagnostic
routing is complete. If the Peerlink module fails more than one test, more
than one indicator will be off.
In the power
-up diagnostic routine, the user
-initiated test, and the
operational test, the outcome of the P/C COMM test depends upon the
status of the P/C. If the P/C is in a fatal error mode, the Peerlink module
interprets this as a P/C COMM test failure. If the P/C COMM indicator is
off at the end of the test, before assuming that there is really a P/C COMM
error
, you should make sure that:
D
V Memory starting address is valid
D
P/C is not in a fatal error mode
D
Connection between the module and the P/C is secure (Check that any
keys used are in the proper slot in the base, and that the module is
firmly seated and latched in place)