Overview
1-6
1.3 PPX:500-5054 & PPX:505-7354–Dual Communication Channels
Peerlink
models PPX:500-5054 and PPX:505-7354 can operate like the
PPX:500-5053, but also offer a dual communication channel option. By
setting a switch on the module, you may use a single communication
channel with both active and passive monitors.
In the dual communication channel option, if one network cable becomes
disabled, communication automatically switches to the other network
cable, allowing network communication to be maintained without
interruption. Communication will always occur on the channel which
detects the most active stations on the network. This model might be
preferable in applications where the Peerlink cables could be easily
damaged.
Figure 1-3 illustrates a typical network using the dual communication
channel option. The passive monitor option is not available when dual
communication channels are used.
Network
Address
#1
N.A.
#2
N.A.
#3
Network
Address
#16
ACTIVE
MONITOR
PEERLINK
MODULE
SERIES
505
P/C
N.A.
= network address
SERIES
500
P/C
SERIES
500
P/C
SERIES
505
P/C
PEERLINK
MODULE
PEERLINK
MODULE
PEERLINK
MODULE
CHANNEL A
CHANNEL B
Figure 1-3
Dual
Channel Network
Page view 14