CC1A7865.1en
31.10.2002
Siemens Building Technologies
HVAC Products
7
865.1
Interface RS-485
RWF40...
The RS-485 interface is used for integrating RWF40… controllers into data networks
via MOD bus protocol.
Application examples:
- Process visualization
- Plant control
- Reporting
Master-slave principle
Communication between a PC (master) and a device (slave) via MOD bus is based on
the master-slave principle in the form of data query / instruction – reply.
A master computer controls the exchange of data and can address up to 99 controllers
via device addresses (slaves).
Page view 0
1 2 3 4 5 6 ... 13 14

Summary of Contents

Page 1 - RWF40

CC1A7865.1en31.10.2002Siemens Building TechnologiesHVAC Products7865.1Interface RS-485RWF40...The RS-485 interface is used for integrating RWF40… cont

Page 2

10/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Address DatatypeAccess Parameter Value range Defaultvalue0x0300 word [13] R / O

Page 3

11/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Address Data type Access Parameter0x0200 word R / O Outputs and statesB15 B14 B

Page 4

12/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Description of operating modesParameter «RemoteStatus» is used to switch betwee

Page 5

13/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002The previous functions of the RWF40... are maintained (apart from memory usage)

Page 6

14/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Modulating controller:The management system predefines the value (degree of mod

Page 7

2/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Transmission mode (RTU)The transmission mode used is the RTU (remote terminal un

Page 8

3/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Communication sequenceBoth the start and end of a data block are characterized b

Page 9

4/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Data query sequenceThe time sequence of a data query looks as follows:MasterSlav

Page 10 - HVAC Products 31.10.2002

5/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Structure of the data blocksAll data blocks use the same structure:Slave address

Page 11

6/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Checksum (CRC16)The checksum (CRC16) is used to detect transmission errors.If th

Page 12

7/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Reading n wordsThis function is used to read n words from a certain address.Slav

Page 13

8/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Writing n wordsSlaveaddressFunction0x10Addressof firstwordNumber ofwordsNumber o

Page 14 - Subject to change!

9/14Siemens Building Technologies CC1A7865.1enHVAC Products 31.10.2002Address tablesAddress DatatypeAccess Parameter Value range Defaultvalue0x0000 fl