Bit Logic Instructions
Statement List (STL) for S7-300 and S7-400 Programming
1-18
A5E00706960-01
1.18 S Set
Format
S <Bit>
Address Data type Memory area
<Bit> BOOL I, Q, M, L, D
Description of instruction
S (set bit) places a "1" in the addressed bit if RLO = 1 and the switched on master
control relay MCR = 1. If MCR = 0, the addressed bit does not change.
Status word
BR CC 1 CC 0 OV OS OR STA RLO /FC
writes: - - - - - 0 x - 0
Example
Power
rail
I 1.0
NO
contact
Q 4.0
Coil
Q 4.0
I 1.0
I 1.1
Q 4.0
0
1
0
1
0
1
Signal state diagrams
Coil
I 1.1
NC
contact
AI 1.0
SQ 4.0
AI 1.1
RQ4.0
Statement List Program
Relay Logic
Page view 29