Siemens Albatros2 AVS37 User Manual Page 99

  • Download
  • Add to my manuals
  • Print
  • Page
    / 135
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 98
99/135
Siemens Switzerland Ltd User Manual CE1U2353en
HVAC Products Configuration 02.06.2009
If the input signal drops below the limit value of 0.15 V, the heating demand is invalid
and therefore has no effect.
Example of pressure measurement 10V
U1 Voltage value 1
F1 Function value 1
U2 Voltage value 2
F2 Function value 2
Example of relative room humidity 10V
Spannung an Hx
U2=10VU1=0V
F
1=0
F2=100
0.15V
Relative Feuchte [%]
U2=5V
U1 Voltage value 1
F1 Function value 1
U2 Voltage value 2
F2 Function value 2
If the measured value is below 0.15V it is regarded as invalid and an error message is
generated.
Example of room temperature 10V
Raumtemperatur [°C]
Spannung an Hx
U2=10VU1=0V
F
1=0
0.15V
F2=100
F2=50
U1 Voltage value 1
F1 Function value 1
U2 Voltage value 2
F2 Function value 2
If the measured value is below 0.15V it is regarded as invalid and an error message is
generated.