Siemens Switzerland Ltd User Manual CE1U2353en
HVAC Products Maintenance / special mode 02.06.2009
Manual operation
Line no. Operating line
7140 Manual control
When manual control is activated, the relay outputs are no longer energized and
deenergized according to the control state but are set to a predefined manual control
state in accordance with their functions (see table below).
The burner relay energized in manual control can be deenergized by the electronic
temperature controller (TR).
Designation Relay State
Solar Collector pump Q5 Off
DHW Charging pump Q3 On
Diverting valve Q3 Off
Mixing pump Q32 Off
Intermediate circuit pump Q33 On
Mixing valve opening /
closing
Y31/Y32 Off
Instantaneous DHW heater
pump
Q34 On
Instantaneous DHW heater
on / off
Y33/Y34 Off
Circulating pump Q4 On
electric immersion heater K6 On
Heating circuit 1...3 heating circuit pump Q2
Q6
Q20
On
Heating circuit mixing valve
opening / closing
Y1 / Y2
Y5 / Y6
Off
Heating circuit pump 2nd
speed
Q21
Q22
Q23
On
Cooling circuit 1 Cooling circuit pump Q24 On
Cooling circuit mixing valve
opening / closing
Y23/Y24 Off
Diverting valve for cooling Y21 Off
Primary controller System pump Q14 On
Mixing valve opening /
closing
Y19/Y20 Off
Hx group Pump H1 Q15 On
Pump H2 Q18 On
Pump H3 Q19 On
Auxiliary functions Alarm output K10 Off
Time program 5 K13 Off
Heat demand K27 On
Refrigeration demand K28 Off
Storage tank transfer pump Q11 Off
After manual control has been activated, a change to the basic display must be made.
There, the maintenance / special mode symbol
appears.
Press the info button to switch to info display “Manual mode“, where the setpoint can be
adjusted.
Simulations
Line no. Operating line
7150 Simulation outside temp
To facilitate commissioning and fault tracing, outside temperatures in the range from –
50 to +50°C can be simulated. During simulation, the actual, the composite and the
attenuated outside temperature will be overridden by the set simulated temperature.
During simulation, calculation of the 3 mentioned outside temperatures continues and
the temperatures are available again when simulation is completed.
The function is deactivated by setting -.- on this operating line, or automatically after a
timeout of 1 hour.
Setpoint adjustment in
manual control