SED2 AOP Operating Instructions
16 Siemens Building Technologies
2. In the Internal mode, scroll through the list of parameter sets until the AOP parameter set
appears. Press
to confirm the selection.
3. Press
again to select All parameters.
4. Use
to access the internal AOP parameters. Internal parameters that display AOP
information include:
Parameter Description Parameter Description
P0964 Software Version Information P8562 Free Memory
P8552 Base slave address P8563 Enable Text Scrolling
P8553 Default baud rate P8564 RS-232 Error count
P8564 Enable Autobaud P8565 RS-485 Error count
P8560 Battery level P8566 Null USS Responses
P8561 Enable Backlight P8567 USS Timeouts
Parameter Upload (Upread)
CAUTION:
Upload/Download Limitations:
The AOP will normally only upload and download parameters up to and including
Level 3. When copying parameter sets between VFDs, you must again complete
the quick commissioning to re-adjust the motor parameters. Exit quick
commissioning with P3900=3 (for only motor data).
Do not exit quick commissioning with P3900=1 or all downloaded parameters
are reset to their default values.
Memory Limitation:
The delivered AOP supports five European languages: English, German, French,
Spanish, and Italian. Due to internal memory limitations, you should delete one
of these languages in order to upload the specified ten parameter sets that
can be held on the AOP.
To Delete a Language:
Select Language from the main menu, highlight the language you want to delete,
and then press
and .
NOTE: Once a language has been removed, it cannot be restored.
The upload/upread procedure reads a parameter set from a SED2 VFD and stores that
parameter set in the internal memory of the AOP. The AOP can read from a single SED2 VFD in
local mode or from one specific SED2 VFD on a network of SED2 VFDs in master mode.
Use the following procedure to upload/upread a parameter set from a SED2 to the AOP: