Siemens RUGGEDCOM RSG2200 Specifications Page 46

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 45
Chapter 6
Certification
RUGGEDCOM RSG2200
Installation Guide
40 EMI and Environmental Type Tests
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RSG2200 meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.
Test Description Test Levels
Enclosure Contact +/-8 kVIEEE C37.90.3 ESD
Enclosure Air +/-15 kV
IEEE C37.90.2 Radiated RFI Enclosure Ports 35 V/m
Signal Ports +/- 4 kV @ 2.5 kHz
DC Power Ports +/- 4 kV
AC Power Ports +/- 4 kV
Fast Transient
Earth Ground Ports +/- 4 kV
Signal Ports 2.5 kV Common Mode @1MHz
DC Power Ports 2.5 kV common, 1 kV
differential mode @ 1 MHz
IEEE C37.90.1
Oscillatory
AC Power Ports 2.5 kV common, 1 kV
differential mode @ 1 MHz
Signal Ports 5 kV (Fail-Safe Relay Output)
DC Power Ports 5 kV
IEEE C37.90 H.V. Impulse
AC Power Ports 5 kV
Signal Ports 2 kVAC
DC Power Ports 1.5 kVDC
IEEE C37.90 Dielectric Strength
AC Power Ports 2 kVAC
Environmental Type Tests
Test Description Test Levels
IEC 60068-2-1 Cold Temperature Test Ad -40 °C (-40 °F), 16 Hours
IEC 60068-2-2 Dry Heat Test Bd 85 °C (185 °F), 16 Hours
IEC 60068-2-30 Humidity (Damp Heat, Cyclic) Test Db 95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60068-21-1 Vibration 2g @ 10-50 Hz
IEC 60068-21-2 Shock 30 g @ 11 ms