Installation
3.2 Installation on a DIN rail
SCALANCE X-300
26 Operating Instructions, 01, A5E01113043
3.2 Installation on a DIN rail
Caution
If the IE Switch -300 is liable to be subjected to severe vibration (> 10 g), use the S7-300
standard rail for installation. The DIN rail does not provide adequate support if vibration
exceeds 10 g.
Installation
Install the IE Switch X-300 on a 35 mm DIN rail complying with DIN EN 50022.
1. Place the upper catch of the IE Switch X-300 over the top of the DIN rail and then push in
the lower part of the device against the rail until it clips into place.
2. Fit the connectors for the power supply.
3. Fit the connectors for the signaling contact.
4. Insert the terminal blocks into the sockets on the IE Switch X-300.
Figure 3-1 IE Switch X-300 installation on a DIN rail (35 mm)
Uninstalling
To remove an IE Switch X-300 from the DIN rail:
1. First disconnect all connected cables.
2. Use a screwdriver to release the lower DIN rail catch of the IE Switch X-300 and pull the
lower part of the IE Switch X-300 away from the rail.