26 Texas Instruments Communication Driver Manual
Dipswitch Settings
The dipswitch block is located at the rear of the CPU. The table below summarizes the dipswitch
settings for the CPU dipswitch.
Switch ON OFF
SW1 CPU Battery CPU battery enabled
SW2 Station Address is 1 Station address is set via MIU (Machine
Interface Unit) or programming software
SW3 Baud rate selection for Serial Interface Port
SW4 Baud rate selection for Serial Interface Port
Dipswitch Settings for Baud Rate
SW3 and SW4 on the dipswitch control the baud rate at which the Serial Interface Port will operate.
Refer to the table below for the baud rates corresponding to the settings of SW3 and SW4.
Baud SW3 SW4
300 Off Off
1200 Off On
9600 On Off
19200 On On