5-11
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
Following power up, the DP/ASi link determines the configuration of the AS
interface and expects a parameterization message and a configuration mes-
sage from the DP master.
The parameterization message is identical to the first seven bytes of the DP
standard part (bytes 0 to 6). You will find a detailed account of the DP stan-
dard part in appendix C.1.
The length of the configuration message for default start-up is exactly 20
bytes and is described in appendix D.1.
Parameterization
and configuration
messages
Configuring the DP/ASi Link