D-8
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
You have an DP/ASi link on which the ASi slave with the highest address to
which outputs are connected is slave 7; the ASi slave with the highest address
to which inputs are connected is slave 12.
Accordingly, the output area has a length of 4 bytes, for slave 7 is located in
the fourth byte. The length ID for the outputs is 03
H.
The input area has a length of 6 bytes, for slave 12 is located in the sixth
byte. The length ID for the inputs is 05
H.
Example of
determining length
IDs
Configuration Message