Page view 34
32 EPHY-MESS Industrial Motor Protection REV201205052
3.5.4 KTY-switching devices of the KTY 04.01-R series
The KTY 04.01-R engine protection equipment with mains and failure
indicator is designed for standard evaluation of engines and machines
provided with a KTY84-1xx sensor and for switch cabinet installation.
The switching device KTY 04.01-R operates in accordance with the
rest current principle and therefore controls itself against rupture of
wire. A short-time voltage loss of less than 200 ms does not lead to a
change of state of the auxiliary contact assemblies.
technical data KTY 04.01-R
mains supply
AC 50 Hz, , -10%...+10%
ambient temperature
-20°C...+60°C
relay output
1 commutator contact potential free
switching capacity
AC 250 V, max 6A; 300 VA cosφ =0,65
type of protection
IP40, terminals IP00
sensor connection
number of measuring circuits
1
type
KTY 84-130
KTY 84-150
KTY 84-151
KTY 84-152
number of connectable sensors
1
switching point
+60°C...+260°C
switch back
10K ± 2,5 K below switching point
fastening
on hat trail
dimensions
75 x 45 x 107.5 mm