REV201205052 EPHY-MESS Industrial Motor Protection 27
3.4.6 Si-sensors, cemented into ceramic / metal sleeve (KH / MH)
For cases of increased mechanical stress the silicon measuring sensors can be cemented into
ceramic or metal sleeves (brass, aluminum or INOX)
Fig. 19, KTY 8x-1xx KH
Technical data KTY 8x-1xx KH / MH
KTY 83-1xx
KTY 84-1xx
*)
insulating material / sensor protection
ceramic sleeve (closed in round or flat form) Isokeralox 99.7 or
brass-, Al-, or INOX-sleeve
operating temperature
-55°C ... +175°C
0°C ... +260°C
dimensions (sensor)
Ø4.9 x 17 (KH), other dimensions upon request
wires
AWG 26/7, 500 mm, PTFE -insulation
feed line colour
according to colour code of the sensor
circuitry system
2-wire system
dielectric strength sensor / wires
3 kV / AC 50 Hz / 1min.
*)
suitable for connection to the EPHY-MESS KTY-switching device