Parameters
List of Parameters
1-186
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Description: Sets the limit value for slip compensation in [%] referred to r0330 (motor rated slip).
Description: Displays the actual compensated slip [%] referred to r0330 (rated motor slip).
Dependency: p1335 > 0 %: Slip compensation active.
Refer to: p1335
Description: Sets the gain for resonance damping for U/f control.
Dependency: Refer to: p1300, p1339, p1349
Note: The resonance damping function dampens active current oscillations that frequency occur under no-load condi-
tions.
The resonance damping is active in a range of approximately 5 ... 90 % of the rated motor frequency (p0310), but
up to a maximum of 45 Hz.
For the open-loop control modes p1300 = 5 and 6 (textile sectors), the resonance damping is internally disabled in
order that the output frequency can be precisely set.
Description: Sets the filter time constant for resonance damping for U/f control.
Dependency: Refer to: p1300, p1338, p1349
p1336[0...n] Slip compensation limit value / Slip comp lim val
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 [%] 600.00 [%] 250.00 [%]
r1337 CO: Actual slip compensation / Slip comp act val
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- [%] - [%] - [%]
p1338[0...n] U/f mode resonance damping gain / Uf Res_damp gain
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 0.00
p1339[0...n] U/f mode resonance damping filter time constant / Uf Res_damp T
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
1.00 [ms] 1000.00 [ms] 20.00 [ms]