Siemens Flush-mount room sensors AQR253... AQR257... CE1P1411en
Building Technologies GAMMA building management systems 2013-04-17
Object Name in ETS I/O
1
Data point type KNX Value range
Index ID Format Unit
Input 1 – up/down 45
D
Input 1/2 – up/down
I, O 1.008 1 bit --- 0 = Up / 1 = Down
Input 1 block 46
Input 1/2 block
I 1.003 1 bit --- 0 = Enable / 1 = Disable
47
E
State contact 2 O 1.001 1 bit --- 0 = Off / 1 = On
48
F
Input 2 - switch I, O 1.001 1 bit --- 0 = Off / 1 = On
49
F
Input 2 – send value I, O 5.001
5.010
1 byte %
---
0…100% (scaled from 0 to 255)
0…255
50
F
Input 2 – switch 2 I, O 1.001 1 bit --- 0 = Off / 1 = On
51
F
Input 2 – send value 2 I, O 5.001
5.010
1 byte %
---
0…100% (scaled from 0 to 255)
0…255
52
G
Input 2 - switch I, O 1.001 1 bit --- 0 = Off / 1 = On
53
G
Input 2 - dim I, O 3.007 4 bit --- 1 = Darker / 9 = Brighter /
0, 8 = Stop
54
H
Input 2 – stopstep I, O 1.007 1 bit --- 0 = Step up / 1 = Step down
55
H
Input 2 – up/down I, O 1.008 1 bit --- 0 = Up / 1 = Down
56 Input 2 block I 1.003 1 bit --- 0 = Enable / 1 = Disable
A, B, C, D, E, F, G, H)
Not all objects at the same time:
For both inputs 1/2 only B, C, or D in case of combined function.
Per input only A, B, C, or D; and E, F, G, or H simultaneously in case of single function.
6.3.6 Fault information
Base module AQR2570 / AQR2576
Object Name in ETS I/O
1
Data point type KNX Value range
index ID Format Unit
Fault information O 219.001 6 bytes --- [0...255 ] = Log no.
[0...2] = Alarm priority
[0...14] = Application area
[0...4] = Fault class
[0...7] = Attribute
[0...7] = Fault state
59
Information on generated fault.
Fault state O 1.001 1 bit --- 0 = Normal / 1 = Faulty 60
Global fault indication. State is “Faulty” if another fault appears.
Fault – configuration O 1.001 1 bit --- 0 = Normal / 1 = Faulty 61
The state changes to “Faulty” if another but the connected front module type was configured. If the front module contains at
least the sensors as configured, no fault is generated..
See sensor for sensor faults.
1)