Siemens Flush-mount room sensors AQR253... AQR257... CE1P1411en
Building Technologies Functionality / Use 2013-04-17
The integrated room humidity controller and room air quality controller can be used
for ventilation control. Both controllers receive up to three switching point values,
one blocking/release object, or a switching signal (e.g. motion detector) via the
bus. When the respective switching point is exceeded, up to three control signals
and one quasi-continuous signal to control the ventilation actuators are transmitted
to other bus members. In addition, a signal with the max. control value from both
controllers is available.
The following table provides information on assessing room air quality based on
the determined CO
2
concentration.
[ppm] Typical CO
2
concentration
<400 Outside air
700 City air
1000 Comfort limit
1500 Ventilation strongly recommended
2000 Inacceptable indoor air quality
4000 Bedroom at poor ventilation
5000 Max. concentration for workspaces (MAC value)
40000 Exhaled air
CO
2
concentration measurements are influenced by air pressure and temperature.
The lower the air pressure, the lower the measured value. Temperature influence is
corrected automatically if a front module with temperature sensor is installed. The
sensor allows for correcting the determined measured value to the prevailing
average air pressure at the mounting location. To do this, altitude [m above sea
level] must be set. The correction has the following effect on an uncorrected
measured value of 1000 ppm at normal conditions (0 m altitude, 25 °C):
Altitude [m] 0 500 1000 1500 2000 2500 3000
CO
2
[ppm] 1000 1095 1201 1317 1445 1586 1740
The room sensor monitors the parameterized sensor variables and the
parameterized front module. An error message is generated if a required sensor
variable does not exist or cannot be measured.
Air quality
measurement and
assessment
(AQR2576…)
Response to errors