Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3182en
Building Technologies Functions 28 May 2009
4.7 Control sequences
4.7.1 Applications and sequences
Application VAV Sequences
Single duct
h ( \ ), c ( / )
Single duct & electrical heater
el.h + c (
\ / )
Single duct & radiator
rad + c ( r\ / ),
Single duct with heat/cool coil
h + c ( \ / )
4.7.2 Sequences overview (setting via parameter P01)
The sequence can be set via parameter P01, if available.
The thermostats can be used in systems featuring:
Heating only mode (P01=0)
Cooling only mode (P01=1)
Manual heating/cooling changeover (P01=2)
Automatic heating/cooling changeover (P01=3)
Heating and cooling mode (e.g. 4-pipe system) (P01=4)
The available modes depend on the application
(selected via DIP switch, see section 4.5).
Parameter
P01 = 0 P01 = 1 P01 = 2 P01 = 3
Sequence
T °C
T °C
T °C
T °C
T
Mode
Available for:
Heating mode Cooling mode
Manually select
heating or
cooling mode
Automatic
heating/cooling
changeover via
external water
temperature
sensor or
remote switch
Single duct
1)
1)
Single duct &
electrical heater
3) 3) 3) 3)
Single duct &
radiator
3) 3) 3) 3)
Single duct with
heat/cool coil
2)
2)
1) Changeover air
2) Changeover water; heat/cool coil
3) The controller operates in heating AND cooling mode. P01 is not available
Notes