Siemens RDG400 Service Manual Page 16

  • Download
  • Add to my manuals
  • Print
  • Page
    / 42
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 15
16 / 42
Siemens RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation CE1P3182en
Building Technologies Functions 28 May 2009
If the button lock function is enabled by parameter P14, then the buttons will be
locked or unlocked by pressing the right button for 3 sec.
If “Auto lock” is configured, then the thermostat will automatically lock the buttons
10 sec after the last adjustment.
The thermostat can be forced into Energy Saving mode, e.g. when a window is
opened. The window contact can be connected to digital input D1 (or
multifunctional input X1, X2). Set parameter P42 (P38, P40) to 3.
The left button switches the operating mode from Energy Saving to Comfort for the
period preset in P68, if the following conditions are fulfilled:
The operating mode switchover contact is closed (connected to input X1, X2,
D1, parameter P38, P40, P42 set to 3)
Parameter P68 (extend Comfort period) is greater than 0
During the temporary Comfort mode extension, timer symbol
appears.
If parameter P68 (extend Comfort period) = 0, extended Comfort cannot be
activated; pressing the left button will show “OFF” (blinking 3 times)
The current operating mode can be forced temporarily into Comfort or Energy
Saving / Protection mode. The time period is adjusted via the rotary knob:
Extend presence: Set the device to Comfort mode for the selected time period
Extend absence: Set the device to Energy Saving / Protection mode for the
selected time period
To activate the function, keep the left button pressed and, within 3 seconds, turn
the rotary knob
clockwise for extended presence
counterclockwise for extended absence
The rotary knob adjusts the time period:
Extend presence: 0.00…+9:30 in steps of 30 minutes; symbol
appears
Extend absence: 0.00…–9:30 in steps of 30 minutes; symbol
or appears
During the extended presence / absence period, timer symbol
appears.
Function
User operating mode
selection
Operating
mode when
activating
function
Function Operating mode
during function
Operating mode at
the end of function
Comf Extension Comf Prot
Comf Absence Prot Comf
Prot Not available - -
Comf Extension Comf Eco
Comf Absence Eco Comf
Eco Extension Comf Eco
Eco Absence Eco Comf
Prot Not available - -
Button lock
Operating mode
switchover contact
(Window contact)
Extended Comfort
mode (operating mode
switchover contact
closed)
Temporary timer for
extension of presence /
absence
Page view 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 41 42

Comments to this Manuals

No comments