Panel PC 677 Panel PC 877
12“ Touch 15“ Touch 19“ Touch 12“ Keys 15“ Keys 15“ Touch 19“ Touch 12“ Keys 15“ Keys
Display
12“ / SVGA (800 x 600) 15“ / XGA (1024 x 768) 19“ / SXGA (1280 x 1024) 12“ / SVGA (800 x 600) 15“ / XGA (1024 x 768) 15" / XGA (1024 x 768) 19" / SXGA (1280 x 1024) 12“ / SVGA (800 x 600) 15“ / XGA (1024 x 768) Size in inches/resolution (pixels)
• / via Remote Kit • / via Remote Kit • / via Remote Kit • / via Remote Kit • / via Remote Kit • / via Remote Kit • / via Remote Kit • / via Remote Kit • / via Remote Kit Centralized / remote-mount
configuration
Control elements
Keyboard
36 with LEDs 36 with LEDs 36 with LEDs 36 with LEDs Function keys
Touch screen (analog/resistive)
Mouse (at front)
General features
Mobile Intel 915GM Express Chipset; Intel Celeron M 370 / 1.5 GHz, 400 MHz FSB, 1 MB SLC; Intel Pentium M 730 /
1.6 GHz, 533 MHz FSB, 2 MBs SLC; Intel Pentium M 760 / 2.0 GHz, 533 MHz FSB, 2 MBs SLC
Intel Pentium 4 technology; Intel Celeron 2.0 GHz; Intel Pentium 4 2.8 GHz;
Intel Pentium 4 Mobile 2.2 GHz
Processor
256 MB, 512 MB, 1 GB, 2 GB 256 MB, 512 MB, 1 GB, 2 GB Main memory
2 x PCI (all slots with card retainers); 1 x Slot for Compact Flash Card 2 x PCI, 2 x PCI/ISA shared, 1 x ISA (all slots with card retainers) Free expansion slots
Windows 2000 Prof. (Multilanguage
2)
), Windows XP Prof. (Multilanguage
2)
), optional without OS Windows 2000 Prof. (Multilanguage
2)
), Windows XP Prof. (Multilanguage
2)
), optionally without OS Operating system
110/230 V AC (wide-range) 50/60 Hz; or 24 V DC 110 V/230 V AC (autorange) 50/60 Hz; or 24 V DC (only in conjunction with Pentium 4 mobile processor) Power supply
Typically 50,000 h (at 24 h continuous operation, depending on temperature) Typically 50,000 h (at 24 h continuous operation, depending on temperature) MTBF of backlight
Drives
3.5" SATA hard disk drive 40 GB, vibration-damped;
optional: 2 x 2.5" SATA hard disk module ( 60 GB), vibration-damped
onboard RAID1 controller
3.5" EIDE hard disk 40 GB, vibration-damped;
Optional: 3.5" EIDE hard disk 80 GB vibration-damped;
Optional: 2 x 2.5" EIDE hard disk module 40 GB, vibration-damped
Optional: RAID1 with 2 x 2.5" SATA hard disk module 60 GB vibration-damped
Hard disk
DVD-R/W
optional; optional optional; optional DVD-ROM; DVD-ROM/CD-R/W
optional via USB; can be ordered as accessory: 1.44 MB 3.5 1.44 MB 3.5“ Floppy disk
Interfaces
onboard, isolated, max. 12 Mbit/s, no plug-in card required, compatible with CP 5611 onboard, isolated, max. 12 Mbit/s, compatible with CP 5611 PROFIBUS/MPI
2 x onboard, 10/100 Mbit/s, RJ45 1 x onboard, 10/100 Mbit/s, RJ45 Ethernet
1 x at front (USB 2.0 high current), 4 x at rear (USB 2.0, of which 2 are high current) 1 x at front (USB 2.0 high current), 2 x at rear (USB 2.0 high current) USB (Universal Serial Bus)
COM1: 1 x V.24 (9-pin) COM1: 1 x V.24 (RS232), COM2: 1 x V.24 (RS232C) Serial interface
optional via PCI plug-in card LPT1 (EPP/ECP) Parallel interface
DVI-I can be used for additional display unit (VGA via adapter) DVI-I can be used for additional display unit (VGA via adapter) Graphics interface
Multimedia
USB; USB PS/2 or USB; PS/2 or USB Keyboard; mouse
Monitoring functions
onboard onboard Temperature, watchdog
Ambient conditions
IP65 (front) acc. to EN60529, NEMA 4 IP65 (front) acc. to EN 60529, NEMA 4 Degree of protection
Tested acc. to DIN IEC 68-2-6: 10 to 58 Hz: 0.075 mm, 58 to 200 Hz: 9.8 m/s
2
(1 g) Tested acc. to DIN IEC 68-2-6: "10 to 58 Hz: 0.075 mm, "58 to 200 Hz: 9.8 m/s
2
(1 g)
Vibration load during operation
Tested acc. to DIN IEC 68-2-29: 50 m/s
2
(5 g), 30 ms, 100 shocks Tested acc. to DIN IEC 68-2-29: 50 m/s
2
(5 g), 30 ms, 100 shocks Shock loading during operation
CE, EN 55011, EN 61000-6-2, EN61000-6-4 CE, EN 55011, EN 61000-6-2, EN 61000-6-4
EMC
+ 5 °C to + 45 °C or + 5 °C bis + 50 °C in installation space, if 40 °C at the front + 5 °C to + 45 °C or + 5 °C to + 50 °C in installation space, if 40 °C at the front
4)
Ambient temperature
during
opera-
tion and at maximum configuration
Tested acc. to DIN IEC 68-2-3, DIN IEC 68-2-30, DIN IEC 68-2-56: 5% to 80% at 25 °C (no condensation) Tested acc. to DIN IEC 68-2-3, DIN IEC 68-2-30, DIN IEC 68-2-56: 5% to 80% at 25 °C (no condensation) Relative humidity
CE, cULus (508) CE, cULus (508) Approvals
With SIMATIC WinCC flexible, SIMATIC WinCC With SIMATIC WinCC flexible, SIMATIC WinCC Packages
Dimensions
400 x 310 483 x 310 483 x 400 483 x 310 483 x 355 483 x 310 483 x 400 483 x 310 483 x 355 Operator control unit (W x H) in mm
368 x 290 x 122 450 x 290 x 120 450 x 380 x 129 450 x 290 x 104 450 x 321 x 123 450 x 290 x 208 450 x 380 x 217 450 x 290 x 191 450 x 321 x 210 Mounting dimensions (W x H x D)
without opt. drives in mm
max. 140 W
1)
max. 140 W
1)
max. 163 W
1)
max. 140 W
1)
max. 140 W
1)
24 V DC
4)
: max. 230 W
5)
230 V AC: max. 300 W
5)
24 V DC
4)
: max. 260 W
5)
230 V AC
4)
: max. 330 W
5)
24 V DC
4)
: max. 230 W
5)
230 V AC: max. 300 W
5)
24 V DC
4)
:max. 230 W
5)
230 V AC: max. 300 W
5)
Power dissipation at maximum
configuration