6 PLC Signals 11.90
6.9.4 Function block FB 65: M STACK and function block FB 66: STACK M
6.9.4 Function block FB 65: M
STACK and
function block FB 66: STACK
M
FB 65
Error number ”F1” in Accu 2 means:
Stack pointer overflow on entering flag
FB 66
Error number ”F1” in Accu 2 means:
Stack pointer too low on removing flag
Note: Maximum nesting depths = 8. If nesting depth >8,
PLC alarm 6114 appears
6.9.5 Function block FB 190
Name: K-LEITPC
D, KH --
D, KY --
D, KY --
A, BY --
ADPR
DBDW
RI/A
MELD
Parameter description of function block FB 190
ADPR Initial address in the DUAL PORT RAM: is not evaluated! (This is on the SIMATIC
side only for reasons of compatibility to the FB 190)
DBDW High byte: Data block number
Low byte: Number of initial word and at the same time initial address in the
link area
RI/A High byte: Transfer direction
0 = Transfer in direction of link area
1 = Transfer in direction of data block
Low byte: Quantity of words to be transferred (<127)
MELD Error messages: 1 Interface fault
(PLC does not change to STOP) 2 DB not available
3 DB too small
4 DB in EPROM
5 0 < data value > 127
6 Wrong direction
255 No fault (FF)
6-26