Introduction
The PAPBH is a gateway that allows a Paradigm Operator Interface access to a PROFIBUS-DP Network. The Host Adapter is connected to the Operator Interface
programming port allowing data transfer with Internal Communications Blocks. The PAPBH is auto-configuring for all PROFIBUS properties such as baud rate, but
needs a Station Address configured by the Operator Interface. These are set up using the PROFIBUS Network Driver described here.
Configuration
The Station Address and Input and Output Data Container Blocks are set in the Configuration Edit dialog from the Select Communications Driver dialog.
The Station Address has a default value of 126 and must be in the range 1 to 125 for normal operation.
The Input and Output Data Container Blocks are the data buffers that the PROFIBUS Network writes data to, and reads data from. These correspond to Internal
Communications Blocks and as such these must be set up in the Communications Block Table. A maximum of 116 words may be transferred per block. Data flow is
described with respect to the PROFIBUS Network - thus Input Data is written to the PROFIBUS Network and Output Data is read from the PROFIBUS Network.
Example
This example shows the PROFIBUS Node configured as Station Address 5, Communications Block A as Input Data and Communications Block B as Output Data.
PROFIBUS DP-SLAVE CONFIGURATION
Name Value
Station Address 5
Input Data Container Block A
Output Data Container Block B
COMMUNICATION BLOCKS
DEVICE ADDRESS DATA TYPE SIZE ACCESS UPDATE LINKS ENABLE
A Internal None
16-bit
Signed
10 Read Auto None Default
B Internal None
16-bit
Signed
10 Read Auto None Default
Communication Block Configuration
Driver Configuration
PROFIBUS NETWORK DRIVER APPLICATION NOTE
Red Lion Controls
20 Willow Springs Circle
York PA 17402
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion UK Ltd
Tapton Park
Chesterfield S41 OTZ
Tel +44 (1246) 22 21 22
Fax +44 (1246) 22 12 22
Red Lion Controls France
56 Boulevard du Courcerin, Batiment 21,
ZI Pariest F-77183 Croissy Beaubourg
Tel +33 (64) 80 12 12
Fax +33 (64) 80 12 13
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship for a period limited to one year from the
date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability
under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company
disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising
out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths,
property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including
without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to
the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The
Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.
Page view 3
1 2 3 4

Comments to this Manuals

No comments