Siemens TL.. Operations Instructions Page 1

Browse online or download Operations Instructions for Hobs Siemens TL... Siemens TL.. Operating instructions User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - SINVERT

SINVERT 350, SINVERT 420 and SINVERT 500 TL Operating Instructions – 11/2009 SINVERT Answers for environment.

Page 2

Description 2.1 Application 10 2 Description 2.1 Application The SINVERT PV inverter is a fully assembled, ready-to-connect inverter unit for PV insta

Page 3

Description 2.1 Application 11 Figure 2-2 SINVERT 420 M Figure 2-3 SINVERT 420 M with doors opened Figure 2-4 SINVERT 500 TL

Page 4

Application 3.1 Scope of delivery 12 3 Application 3.1 Scope of delivery The scope of delivery includes: • Inverter cabinet with • PROFIBUS cable

Page 5

Application 3.2 Dimensions and weights 13 3.2 Dimensions and weights The inverters have the following weights and dimensions (with and without transpo

Page 6

Application 3.3 Configuration of the inverters 14 3.3 Configuration of the inverters The following is the preferred configuration for the SINVERT 140

Page 7

Application 3.3 Configuration of the inverters 15 The following is the preferred configuration for the SINVERT 700 MS (two SINVERT 350 in parallel), S

Page 8 - 1 Introduction

Application 3.4 Medium-voltage components 16 3.4 Medium-voltage components Figure 3-4 Configuration of medium- and low-voltage components Figure 3

Page 9 - 1.1 About this documentation

Application 3.4 Medium-voltage components 17 Figure 3-6 Pressure relief for medium-voltage switchgear Covers for pressure relief openings and associ

Page 10 - 2 Description

Application 3.5 Footprint 18 3.5 Footprint The following diagram shows the inverter footprint: Figure 3-7 Footprint of SINVERT 350, 420, or 500 TL

Page 11

Application 3.6 Installation requirements 19 3.6 Installation requirements The base of the inverter station must have sufficient capacity to carry the

Page 12 - 3 Application

SINVERT SINVERT 350, SINVERT 420 and SINVERT 500 TL Operating Instructions Edition 11/2009 Introduction 1 Description 2 Application 3 Instal

Page 13 - 3.2 Dimensions and weights

Application 3.7 Ambient conditions 20 3.7 Ambient conditions 3.7.1 Storage Table 3-4 Ambient conditions for storage Ambient temperature -25 °C to 70

Page 14 - Application

Application 3.8 Cooling air inlet 21 3.8 Cooling air inlet The inverters must be provided with cooling air through the floor. The required floor cuto

Page 15

Application 3.9 Cooling air flow for inverters 22 3.9 Cooling air flow for inverters For air intake from below, the inverter must be installed above

Page 16

Application 3.9 Cooling air flow for inverters 23 Figure 3-10 Example: Airflow in an inverter station Figure 3-11 The use of air channels for inver

Page 17

Application 3.10 Cable entry 24 3.10 Cable entry The required cable entries for an inverter are: • 8 x 95-300 mm² single core; four DC 250 A inputs •

Page 18 - 3.5 Footprint

Application 3.11 Grounding and lightning protection 25 3.11 Grounding and lightning protection Building lightning strike protection is described in I

Page 19

Application 3.11 Grounding and lightning protection 26 3.11.2 Lightning protection A lightning protection system consists of an external lightning pro

Page 20 - 3.7 Ambient conditions

Application 3.12 Delivery of the inverters 27 3.12 Delivery of the inverters Please check that the consignment is complete against the accompanying d

Page 21 - 3.8 Cooling air inlet

Application 3.13 Storage 28 3.13 Storage For the storage of the inverter units, the following conditions must be strictly observed. • The inverters

Page 22

Application 3.14 Shipping 29 3.14 Shipping In the following sections, note the following: • "Transportation unit" refers to the converter c

Page 23

Safety instructions These Operating Instructions contain information which you should observe to ensure your own personal safety as well as to protec

Page 24 - 3.10 Cable entry

Application 3.14 Shipping 30 Before moving the converter boxes to their final installation site, it is recommended that the cable for the DC input an

Page 25

Application 3.14 Shipping 31 3.14.1 General safety guidelines Pay attention to the safety-related instructions in this section and on the packaging f

Page 26

Application 3.14 Shipping 32 Tipping the cabinet too far can cause it to topple over and may damage the transport pallet (see figure 3-3). Tipping the

Page 27

Application 3.14 Shipping 33 3.14.2 Center of gravity marking The transport unit/cabinet is heavy. The center of gravity is in the upper half of the

Page 28 - 3.13 Storage

Application 3.15 Moving the cabinets 34 3.15 Moving the cabinets The transport unit/cabinet should be transported with extreme care. Driving over bum

Page 29 - 3.14 Shipping

Application 3.15 Moving the cabinets 35 3.15.1 Lifting the DC and drive cabinet The combined DC and drive cabinet can be lifted completely using a cr

Page 30

Application 3.15 Moving the cabinets 36 Figure 3-21 Transport by forklift Figure 3-22 Impermissible transport by forklift: Loading from the front s

Page 31

Application 3.15 Moving the cabinets 37 3.15.2 Lifting the SINVERT 350 and SINVERT 420 AC cabinet If the AC cabinet is to be lifted with a crane, a s

Page 32

Application 3.15 Moving the cabinets 38 3.15.3 Lifting the SINVERT 500 TL AC cabinet The SINVERT 500 TL AC cabinet can be lifted with a crane. To do

Page 33

Application 3.15 Moving the cabinets 39 3.15.4 Lifting the cabinet off the transport pallet The cabinets are attached to the pallet by means of trans

Page 34 - 3.15 Moving the cabinets

Contents 1 Introduction... 8 1.1 About this d

Page 35

Application 3.15 Moving the cabinets 40 Use a crowbar to lift the cabinet so that you can place the rollers under the frame. If you want to change the

Page 36 - 3.15 Moving the cabinets

Installation 4.1 Installation requirements 41 4 Installation 4.1 Installation requirements To ensure the installation of the inverter under the right

Page 37

Installation 4.2 Mechanical installation 42 4.2 Mechanical installation CAUTION Danger of mechanical damage The forces occurring during transport may

Page 38

Installation 4.2 Mechanical installation 43 4.2.1 Screwing the transport units together When the cabinets have been placed in their final position, t

Page 39

Installation 4.2 Mechanical installation 44 4.2.2 Bolting the cabinets to the floor Information on the attachment holes can be found in the floor pla

Page 40

Installation 4.3 Electrical installation 45 4.3 Electrical installation Installation of cables Cables that can cause disruptions or are themselves vul

Page 41 - 4 Installation

Installation 4.3 Electrical installation 46 4.3.1 Observe the five safety rules For your personal safety and to avoid damage, the following safety in

Page 42 - 4.2 Mechanical installation

Installation 4.3 Electrical installation 47 4.3.2 External cable connections The following cable connections should be made: Table 4-1 External cabl

Page 43 - Installation

Installation 4.3 Electrical installation 48 4.3.3 Connecting the power cables and control cables Remove all fuses for the AC main power supply to the

Page 44

Installation 4.3 Electrical installation 49 Copper rail on the drive and prepared cable Cable connected, ferrite rings attached Figure 4-4 Cable

Page 45 - 4.3 Electrical installation

4.4 Communication ... 57 4.4.1 Profibus ...

Page 46

Installation 4.3 Electrical installation 50 Connection inverter – DC link In a master/slave combination, connect the DC link to the supplied cables (2

Page 47

Installation 4.3 Electrical installation 51 CAUTION The configuration of the inverters according to chapter 3.3 should be taken into account for the

Page 48

Installation 4.3 Electrical installation 52 AC main power supply Connect the AC cables (going towards the MS transformer) and the PEN conductor. Ensu

Page 49

Installation 4.3 Electrical installation 53 AC auxiliary power (self/external supply) The SINVERT 350/420 inverters have a self-supply option (deliver

Page 50

Installation 4.3 Electrical installation 54 Figure 4-14 Position of the terminal strip -OPT in the SINVERT 500 TL

Page 51 - CAUTION

Installation 4.3 Electrical installation 55 DC input Connect the DC cables (corresponding to the connection drawings and the cable list). Ensure the c

Page 52

Installation 4.3 Electrical installation 56 Internal control cable Plug in the connector in the AC cabinet (for the control cable coming from the driv

Page 53

Installation 4.4 Communication 57 4.4 Communication Communications cables and sensors should be connected only by people with the appropriate electric

Page 54

Installation 4.4 Communication 58 4.4.1 Profibus If you have a system in master-slave combination, you must route the Profibus cable between the inver

Page 55

Installation 4.4 Communication 59 4.4.2 RS422/Ethernet In a master/slave combination, the RS422 bus cable must be laid between the inverters. All inve

Page 56

Figures Figure 2-1 Overview of PV system ... 10 Figure 2-2 SINVERT 420 M

Page 57 - 4.4 Communication

Support 5.1 Contact addresses 60 5 Support 5.1 Contact addresses The support hotline for SINVERT can be reached via the contact methods listed below f

Page 58

Siemens AG Industry Sector, IA SE S PV P.O. Box 2355 90713 Fuerth GERMANY Subject to change © Siemens AG 2009 www.siemens.de/sinvert Further inf

Page 59 - Figure 4-22 Com server

Figure 4-2 Screwing together transportation units... 43 Figure 4-3 Accessory kit ferrite rings...

Page 60 - 5 Support

Introduction 1.1 About this documentation 8 1 Introduction 1.1 About this documentation This manual will provide you with guidance in the use of SINV

Page 61 - Further information

Introduction 1.1 About this documentation 9 1.1.2 Target group This documentation contains information of interest to the following target groups: •

Comments to this Manuals

No comments