ADJUSTMENTS BEFORE FIRST FIRING
Adjustment of the combustion head, and air and gas
deliveries has been illustrated on page 8.
In addition, the following adjustments must also be
made:
- Open manual valves up-stream from the gas train.
- Adjust the low gas pressure switch to the start of the
scale (A).
- Adjust the high gas pressure switch to the end of the
scale (B).
- Adjust the air pressure switch to the zero position of
the scale (C).
- Purge the air from the gas line.
Fit a U-type manometer (D) to the gas pressure test
point on the sleeve.
The manometer readings are used to calculate the
MAX. burner power using the diagram on page 6.
Before starting up the burner it is good practice to adjust
the gas train so that ignition takes place in conditions of
maximum safety, i.e. with gas delivery at the minimum.
(D)
(A)
LOW GAS PRESSURE SWITCH AIR PRESSURE SWITCHHIGH GAS PRESSURE SWITCH
(B) (C)
D2368