COMBUSTION HEAD ADJUSTMENT
Installation operations are now at the stage where the
blast tube and sleeve are secured to the boiler as shown
in fig. (A). It is now a very simple matter to set up the
combustion head, as this depends solely on the maxi-
mum output developed by the burner.
It is therefore essential to establish this value before pro-
ceeding to set up the combustion head.
There are two adjustments to make on the head:
• outside air R1;
• central air R2.
In diagram (C) find the notch for:
Outside air adjustment R1 (A)
Turn screw 4)(A) until the notch identified is aligned with
the front surface 5)(A) of the connector.
Central air adjustment R2 (B)
Loosen the 3 screws 1)(B) and turn ring 2) until the
notch identified is aligned with index 3). Tighten the 3
screws 1) fully down.
Example
RS 160 /M LN
max. burner output = 5681 MBtu/hr
If we consult diagram (C) we find that for this output the
adjustments are:
• outside air: R1 = notch 8.6;
• central air: R2 = notch 0.
NOTES
• R2 adjustment (diagram C) is an indication only. If
possible, always keep the ring nut closed (notch 0); if air
recovery is required the nut may be opened following
the indications in diagram (C).
• Diagram (C) indicates an optimal regulation for a type
of boiler seen in fig. (B) page 5.
Make sure that the combustion characteristics are satis-
factory and free of pulsations.
Once you have finished setting up the head, refit the
burner to the slide bars 3)(D) at approximately 4” from
the sleeve 4)(D) - burner positioned as shown in fig. (B)
pag. 7 - insert the flame rod cable and the ignition elec-
trode cable and then slide the burner up to the sleeve so
that it is positioned as shown in fig. (D).
Refit screws 2) on slide bars 3) after mounting the
extension bracket and relative extensions.
Secure the burner to the sleeve by tightening screw 1).
Reconnect the swivel joint 7) to the graduated sector 6).
Connect gas train and pilot train as shown in fig. (A)
page 9.
Important
When fitting the burner on the two slide bars, it is advis-
able to gently draw out the high tension cable and flame
detection probe cable until they are slightly stretched.
IMPORTANT: In order to facilitate adjustment,
loosen screw 6)(A), adjust and then tighten.
(A)
(C)
(B)
Notches (Air = Gas)
Burner max output
(D)
D2801
D1707
D2367