Siemens FC10 Operations Instructions Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
Structure and function
13
Siemens Building Technologies 007995_a_en_--.doc
Fire & Security Products 04.2004
4.2.4 Alarms
An alarm is triggered when:
a manual call point has been activated,
an automatic detector has detected a fire.
The process in case of alarm depends on:
the operating mode set ('Manned' or 'Unmanned');
the zone type selected (internal, via timer V1 and V2 or direct)
The following figure shows the processing of alarms:
‘V1’
state ‘ALARM 1’
zone output activated
start timer ‘V1’
Decision
ALARM
mode ‘manned’
ALARM
manual call point zone
mode ‘manned’
no influence
state ‘ALARM 2’
Buzzer & sounders (re-) activated
control lines(re-) activated
contact RT-Alarm activated
Reset
V1 expired ?
acknowledged ?
V2 expired ?
fire ?
minor incident ?
Start timer ‘V2’
Zone type ‘via timer V1/V2’ Zone type ‘direct
ALARM
mode ‘unmanned
state ‘ALARM 0’
buzzer activated
sounders activated
zone output activated
ALARM
mode ‘manned’
no influence
Zone type ‘internal’
activate next call point
or
press key
‘cancel alarm delay’
no fire zone
fire detector zone
fire detector zone
buzzer activated (continuous)
sounders activated
Fig. 3 Flow diagram in case of alarm
Process: Zone type direct
In case of alarm, the fire brigade is called up immediately.
Process: Zone type via timer V1 and V2
With this zone type, the process depends on the operating mode set. As a rule:
in operating mode 'Unmanned'
In case of alarm, the fire brigade is called up immediately.
in operating mode 'Manned'
During V1 the staff may acknowledge the alarm. During V2 the staff may check
whether it is a real fire or false alarm.
Process: Zone type internal
Alarm is only indicated on the control unit, it is not transmitted to the fire brigade.
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 31 32

Comments to this Manuals

No comments