Siemens SICLOCK TC 400 Operations Instructions Page 85

  • Download
  • Add to my manuals
  • Print
  • Page
    / 138
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 84
Parameterization
9-84
© Siemens AG 2007 All Rights Reserved
SICLOCK
®
TC400
9.2.2 SIMATIC method
The four Ethernet ports support the SIMATIC method with four protocols:
PCS7-compatible mode
S5-compatible mode
A parameter is available for each Ethernet port.
/SIMATIC Method/Ethernet 1 (0.15.01)
parameter
/SIMATIC Method/Ethernet 2 (0.15.02)
parameter
/SIMATIC Method/Ethernet 3 (0.15.03)
parameter
/SIMATIC Method/Ethernet 4 (0.15.04)
parameter
Mode
The parameter entry /SIMATIC Method/Ethernet 1/mode (0.15.01) sets the send
clock between 0 s, 1 s and 10 s.
Send condition
The parameter entry /SIMATIC Method/Ethernet 1/send condition (0.15.01) spec-
ifies whether the signal should always be output or only if synchronized.
Destination address
The parameter entry /SIMATIC Method/Ethernet 1/destination address (0.15.01)
specifies the send address of the SIMATIC method. Typically the broadcast
address FF:FF:FF:FF:FF:FF is set.
Page view 84
1 2 ... 80 81 82 83 84 85 86 87 88 89 90 ... 137 138