SIMATIC S7-400
Function modules
FM 450-1 counter module
6/116
Siemens ST 70 · 2011
■
Overview
• Two-channel intelligent counter module for simple counting
tasks
• For direct connection of incremental encoders
• Comparison function with 2 specifiable comparison values
• Integrated digital outputs for outputting the response when the
comparison values are reached
Note:
SIMODRIVE Sensor/Motion Connect 500 feature incremental
encoders and preassembled connecting cables for counting
and positioning functions.
www.siemens.com/simatic-technology
■
Technical specifications
6ES7 450-1AP00-0AE0
Supply voltages
Aux. voltage 1L+, load voltage 2 L+
• Rated value (DC) 24 V
• permissible range, lower limit (DC) 20.4 V; dynamic 18.5 V
• permissible range, upper limit
(DC)
28.8 V; dynamic 30.2 V
• non-periodic skip
- Duration 500 ms
- Recovery time
50 s
- Value
35 V
Load voltage 1L+
• Reverse polarity protection Yes
Load voltage 2L+
• Reverse polarity protection Yes
Current consumption
from load voltage 1L+ (without
load), max.
40 mA
from backplane bus 5 V DC, max. 450 mA
Power losses
Power loss, typ. 9W
Connection method
required front connector 1x 48-pin
Digital inputs
Number of digital inputs 6
Functions 1 for gate start, 1 for gate stop,
1 for setting the counter
Input voltage
• for signal "0" -28.8 to +5 V
• for signal "1" +11 to +28.8 V
Input current
• for signal "1", typ. 9mA
Input delay (for rated value of input
voltage)
• Input frequency (with a time delay
of 0.1 ms), max.
200 kHz
• for standard inputs
- parameterizable Yes
- at "0" to "1", max. 2.5 μs; >= 2.5 μs (200 kHz);
<= 25 μs (20 kHz)
Digital outputs
Number of digital outputs 6
Short-circuit protection
Yes; Clocked electronically
Limitation of inductive shutdown
voltage to
2L+ (-39 V)
Output voltage
• for signal "0" (DC), max. 3V
• for signal "1", min. 2L+ (-1.5 V)
Output current
• for signal "1" rated value 0.5 A
• for signal "1" permissible range for
0 to 60 °C, min.
5mA
• for signal "1" permissible range for
0 to 60 °C, max.
0.6 A
Output delay with resistive load
• 0 to "1", max. 300 μs
© Siemens AG 2011
© Siemens AG 2011