Bulletin SIB2.7-8Sensitrip®MD & ND-FrameInformation andInstruction GuideI-T-E® Molded CaseCircuit Breakers

Page 2

8MD and ND-Frame Trip AdjustmentsFigure 1In = Maximum circuit breaker ampere rating.Ir = Current Rating—a function of continuous ampere adjust-ment se

Page 3 - 3-Pole, 600-1200 Amperes

MD and ND-Frame Trip Adjustments9Figure 1In = Maximum circuit breaker ampere rating.Ir = Current Rating—a function of continuous ampere adjust-ment se

Page 4 - IMPORTANT

10MD and ND-Frame Time Current Curve600-1000A With Short Time Delay Set on Fixed Time

Page 5 - Information and Instructions

MD and ND-Frame Time Current Curve111200A With Short Time Delay Set on Fixed Time

Page 6

12MD and ND-Frame Time Current Curve600-100A With Short Time Delay Set on I2t

Page 7 - Installation of Breaker

MD and ND-Frame Time Current Curve131200A With Short Time Delay Set on I2t

Page 8

14MD and ND-Frame Time Current Curve600-100A Without Short Time Settings

Page 9 - Adjustable Long Time Delay

MD and ND-Frame Time Current Curve151200A Without Short Time Settings

Page 10 - Adjustable Short Time Delay

16MD and ND-Frame Time Current CurveGround Fault Trip Data

Page 11

MD and ND-Frame Time Current Curve17Example

Page 13

18MD and ND-Frame Let-Thru Curves

Page 14

I-T-E Connecting Studs (RS5785, RS5786)19GeneralThese connecting studs can be used on 3-pole circuitbreakers and on line and load terminals. Both the

Page 15

20I-T-E Connecting Studs (RS5785, RS5786)Circuit Breaker PreparationA. Remove terminal shield (1) from line and load side ofbreaker frame. Two #8-32 s

Page 16

I-T-E Connecting Studs (RS5785, RS5786)21F Remove the positioning template.G. Mount the circuit breaker by positioning it over the rearbusbar mounting

Page 17

22I-T-E Pressure Wire ConnectorsGeneralNOTE: This instruction outlines the recommended installationprocedure for all MD and ND Frame pressure wireconn

Page 18 - Ground Fault Trip Data

I-T-E Pressure Wire Connectors23Connector(2) CatalogNumbersCircuit Breaker AmpereRating (In)Connector Wire Range Set Screw Torque For Use With Type(s)

Page 19

24I-T-E Compression Connectors (CCM800, CCN1200)GeneralNOTE: This instruction sheet outlines the recommendedinstallation procedure. Use of lugs may re

Page 20

I-T-E Compression Connectors (CCM800, CCN1200)25Figure 3K. Position connector tang on top of the circuit breakerterminal pad and secure with 3/8-16 X

Page 21 - Figure 2

26I-T-E Handle Blocking Device (MN6BL)GeneralThe handle blocking device, MN6BL, is provided to permitblocking the toggle handle of an MD and ND-Frame

Page 22

I-T-E Handle Padlocking Device (MN6HPL)27GeneralThe padlocking device, MN6HPL, consists of the handleblocking device (3) and an additional component (

Page 23 - Figure 6

I-T-E MD and ND-Frame Circuit Breakers3-Pole, 600-1200 AmperesTypes SMD6, SND6, SHMD6, SHND6, SCMD6, SCND6Digital Solid State Circuit BreakersTable of

Page 24

28I-T-E Plug-In AdaptersNOTE: Plug-in adapters are for use only with MD-Frame.GeneralA complete plug-in installation requires one line end adapterasse

Page 25

Installation Diagrams29

Page 26

30I-T-E Mechanical Interlock (M15404)Figure 1Circuit Breaker PreparationA. Turn off and lock out all power supplying circuit breakeror frame before re

Page 27 - Figure 4

I-T-E Mechanical Interlock (M15404)31Support Tie Bar MountingA. With 9-in. long tie bar wrench (8) supplied (Figures 2 and3) positioned around left po

Page 28

32I-T-E Mechanical Interlock (M15404)D. Using tie bar wrench carefully positioned over tie barconnector, (so as not to damage support tie bar assem-bl

Page 29

I-T-E Mechanical Interlock (M15404)33Figure 7

Page 30 - I-T-E Plug-In Adapters

34I-T-E Internal AccessoriesCircuit Breaker PreparationA. Turn power off supplying device before installing kit.B. Make sure device is in tripped posi

Page 31 - Installation Diagrams

I-T-E Internal Accessories35Figure 3C. Check handle for proper fit on handle arm. Replace loadend cover and cover screws. (quantity 8)Replace All Cove

Page 32 - Circuit Breaker Preparation

36I-T-E Internal AccessoriesMechanical and Electrical CheckShunt TripA. Reset and turn circuit breaker ON.B. Attach test circuit to accessory leads. W

Page 33

I-T-E Internal Accessories37Auxiliary Switch Identification (All With Three Leads)WireMarkingsWireColorSwitch Terminals or ContactsC1 or C2 White C. -

Page 34 - Rocker Arm Mounting

2IMPORTANTThe information contained herein is general in nature and is not intended forspecific application purposes nor is it intended as a training

Page 35 - Figure 7

38I-T-E Rotary Handle OperatorTypes 1, 3R, 4, 4X, 12Standard Depth (RHONSD)Variable Depth (RHONVD)GeneralWhen properly installed, the rotary handle op

Page 37

40I-T-E Max-FlexTM Flange-Mount Handle OperatorTypes 1, 3R, 4, 4X, 12General InformationThe l-T-E Max-Flex Flange-Mount Handle Operator is a flex-ible

Page 38

Assembly Instructions41MD and ND-Frame ApplicationA complete kit consists of handle, cable and breaker operatorThe handle can be mounted on either rig

Page 39

42I-T-E Max-FlexTM Flange-Mount Handle OperatorTypes 1, 3R, 4, 4X, 12D. Place the plastic washer and connecting link onto thebellcrank pin (7). Secure

Page 40 - I-T-E Rotary Handle Operator

Assembly Instructions43B. Remove the lower terminal shield (14) from the circuitbreaker and punch and drill out the two .56 in. diameterknockouts .C.

Page 41

44I-T-E Max-FlexTM Flange-Mount Handle OperatorCable AdjustmentA. Check that the circuit breaker turns OFF and ON bymoving the operating handle up for

Page 42 - Flange-Mount Handle Operator

I-T-E TELEMAND® Electric Motor Operator45GeneralThe motor operated mechanism is designed to open, closeand reset a circuit breaker or switch by remote

Page 43 - Assembly Instructions

46I-T-E TELEMAND® Electric Motor OperatorF. With the circuit breaker handle in the OFF position, alignthe motor operator mechanism rollers (indicator

Page 44

Installation Diagrams47

Page 45

Information and Instructions3GeneralMD and ND-Frame Solid State Sensitrip style breakers of theSentron family, as shown on page 5, are for use in indi

Page 46 - Flange-Mount Handle Operator

48I-T-E Panelboard Connecting Straps(1)

Page 47 - Electric Motor Operator

I-T-E Enclosures49Type 1- MND61General purpose indoor, sheet-steel enclosure for use innormal atmosphere, listed as service-entrance equipment.Type 12

Page 48

General InformationThese door latch mechanisms are for use in standard orcustom built enclosures. The door latch post assemblies andthe door catch are

Page 49

Installation Diagrams51

Page 50

52MD and ND-Frame Neutral Sensing TransformerGeneralThe I-T-E Neutral Sensing Transformers are available in 600,700, 800, 1000, and 1200 amp ratings.

Page 51 - I-T-E Enclosures

MD and ND-Frame Neutral Sensing Transformer53Figure 3Cable System MountingNOTE: Neutral sensor transformer mounting on cable sys-tems can be done with

Page 52 - Adjusting the Mechanism

54MD and ND-Frame Universal Test Kit (TS-31)Caution: Remove electrical loads from the circuit breaker tobe tested prior to performing tests. Failure t

Page 53

MD and ND-Frame Universal Test Kit (TS-31)55Enter Test to performH. If you press ENTER, you will be prompted for the phaseto test: The TS-31 will disp

Page 54 - Bus Bar System Mounting

56Ordering InformationCircuit Breaker Catalog NumbersSMD63-Pole, 600V ACCatalog NumberMax.Cont.CurreRatingCont.CurrentSettingLongTimeDelayInstantaneou

Page 55 - Cable System Mounting

Ordering InformationCircuit Breaker Catalog Numbers57SND63-Pole, 600V ACCatalog NumberMax.Cont.CurreRatingCont.CurrentSettingLongTimeDelayInstantaneou

Page 56 - Operating Instructions

4I-T-E Sensitrip Digital Circuit BreakerMD and ND-Frame Outline Drawings(1)3-Pole

Page 57

58# TitleShunt Trip Control Voltage 1 Shunt Trip 1Shunt Trip and1 Auxiliary SwitchAC DC Catalog Number Catalog Number120208240277480600S01MN6S02MN6S03

Page 58 - Ordering Information

Ordering InformationAdditional Accessories59Item Catalog No.Extension Handle EX9Mounting Screw Kit MSMNPressure Wire Connectors(4 pcs.) 250-500 MCM Cu

Page 59

60UL Listings and File NumbersIndustry SpecificationsI-T-E Items UL-489FileNumberCSA ReportNumberBreakersTerminal ConnectorsPlug-ln ConnectorsRear Stu

Page 60 - Bell Alarm Switch

Siemens Energy& Automation, Inc.3333 State Bridge Rd.Alpharetta, GA 30201Bulletin SIB2.7-8 (New) (c) 1990 Siemens Energy & Automation, Inc.

Page 61

I-T-E MD and ND-Frame Installation Instructions5GeneralNOTE: This instruction page outlines the recommendedinstallation procedure.The MD and ND Frame

Page 62 - UL Listings and File Numbers

6MD and ND-Frame Trip Adjustments

Page 63 - Alpharetta, GA 30201

MD and ND-Frame Trip Adjustments7Figure 1In = Maximum circuit breaker ampere rating.Ir = Current Rating—a function of continuous ampere adjust-ment se

Comments to this Manuals

No comments