Siemens DTU3005-B User Manual

Browse online or download User Manual for Unknown Siemens DTU3005-B. Siemens DTU3005-B User's Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - DTU3005-B

DTU3005-BIntelligent Data Transfer Device for Connection to PLCs and Modbus NetworksOperator’s Manual

Page 2

2 Installing the Software6 Siemens Energy & Automation, Inc.2 Installing the SoftwareThe DTU3005 Editor software can be installed fromthe DOS prom

Page 3 - Table of Contents

2 Installing the Software7 Siemens Energy & Automation, Inc.returns you to the DOS prompt as shown in theexample screen below.7. If you are runnin

Page 4

3 Starting the Software8 Siemens Energy & Automation, Inc.3 Starting the SoftwareTo start the DTU3005 Editor software, follow thesesteps:1. If you

Page 5 - 1 Introduction

3 Starting the SoftwareSiemens Energy & Automation, Inc. 93.2 Main MenuThe main menu is located on the top line of thescreen. In addition to th

Page 6

3 Starting the Software10 Siemens Energy & Automation, Inc.3. Type in a name for the project up to eight lettersand numbers in the Project Name: f

Page 7

3 Starting the SoftwareSiemens Energy & Automation, Inc. 114. To select a project type, highlight the type andeither press Enter or click the l

Page 8

4 Creating Project Files—PLC to Devices12 Siemens Energy & Automation, Inc.4 Creating Project Files—PLC to DevicesThis chapter covers configuratio

Page 9

4 Creating Project Files—PLC to DevicesSiemens Energy & Automation, Inc. 13• Device Command Registers—allows you to indicatewhich PLC registers

Page 10 - 2 Installing the Software

4 Creating Project Files—PLC to Devices14 Siemens Energy & Automation, Inc.To select the PLC connected to port 1, highlight PLC Pro-tocol and pres

Page 11

4 Creating Project Files—PLC to DevicesSiemens Energy & Automation, Inc. 15program displays an entry box for the RTS delay time.Enter the time

Page 12 - 3 Starting the Software

SUMMARYThese instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in c

Page 13

4 Creating Project Files—PLC to Devices16 Siemens Energy & Automation, Inc.Saving Port 2 Configuration InformationOnce you have entered all the co

Page 14

4 Creating Project Files—PLC to DevicesSiemens Energy & Automation, Inc. 174.6 Device List SetupThe Device List menu item enables you to indica

Page 15

4 Creating Project Files—PLC to Devices18 Siemens Energy & Automation, Inc.3. Select the device from the list by pressing Enter or thespacebar. Th

Page 16 - 4.1 Application Description

4 Creating Project Files—PLC to DevicesSiemens Energy & Automation, Inc. 196. Enter the beginning register number in the Real-TimeData Register

Page 17 - 4.3 PLC Setup—Port 1

4 Creating Project Files—PLC to Devices20 Siemens Energy & Automation, Inc.4. Select a data register on the list and press Enter to seea list of a

Page 18

4 Creating Project Files—PLC to DevicesSiemens Energy & Automation, Inc. 215. Select the data word (16 bit data) from the list andpress Enter.

Page 19 - 4.4 Device Setup—Port 2

4 Creating Project Files—PLC to Devices22 Siemens Energy & Automation, Inc.3. Select a data item and press Enter to see a list ofdevice real time

Page 20 - 4.5 Passthrough Setup—Port 3

4 Creating Project Files—PLC to DevicesSiemens Energy & Automation, Inc. 23To conserve registers when using VDEW devices, youshould set all unu

Page 21 - 4.6 Device List Setup

4 Creating Project Files—PLC to Devices24 Siemens Energy & Automation, Inc.The relevant status codes (Text #) are listed below.Table 4.1 7SJ600 Re

Page 22

4 Creating Project Files—PLC to DevicesSiemens Energy & Automation, Inc. 25Once you are finished entering data, select Save to saveyour configu

Page 23 - Registers

Table of ContentsSiemens Energy & Automation, Inc. i1 Introduction ...11.1 Product Overview...

Page 24

4 Creating Project Files—PLC to Devices26 Siemens Energy & Automation, Inc.parameter is used only with Allen-Bradley PLCs. Itspecifies the file nu

Page 25 - Registers by Device

4 Creating Project Files—PLC to DevicesSiemens Energy & Automation, Inc. 274. Enter the value for the Command Block Read Delay.This is the dela

Page 26

5 Creating Project Files—Modbus Master to Devices28 Siemens Energy & Automation, Inc.5 Creating Project Files—Modbus Master to DevicesThis chapter

Page 27

5 Creating Project Files—Modbus Master to DevicesSiemens Energy & Automation, Inc. 295.2 Configuring the Project FileOnce you have created or o

Page 28

5 Creating Project Files—Modbus Master to Devices30 Siemens Energy & Automation, Inc.5.3 Modbus Setup—Port 1You must have a Modbus Master to Devic

Page 29 - 4.9 Global Command Registers

5 Creating Project Files—Modbus Master to DevicesSiemens Energy & Automation, Inc. 31Select either ASCII or RTU as your Modbus protocol,then pr

Page 30 - 4.11 Device Command Registers

5 Creating Project Files—Modbus Master to Devices32 Siemens Energy & Automation, Inc.5.4 Device Setup—Port 2One or more Siemens devices may be con

Page 31 - 4.12 Saving the Project File

5 Creating Project Files—Modbus Master to DevicesSiemens Energy & Automation, Inc. 335.5 Modbus/Passthrough Setup—Port 3Port 3 can be used for

Page 32 - Master to Devices

5 Creating Project Files—Modbus Master to Devices34 Siemens Energy & Automation, Inc.Passthrough to Port 2 (SEAbus)If you select Passthrough to Po

Page 33

5 Creating Project Files—Modbus Master to DevicesSiemens Energy & Automation, Inc. 355.6 Device List SetupThe device list menu item enables you

Page 34 - 5.3 Modbus Setup—Port 1

Table of Contentsii Siemens Energy & Automation, Inc.© Copyright 1999 Siemens Energy & Automation, Inc.SIEMENS is a registered trademark of Si

Page 35 - Response Time-Out

5 Creating Project Files—Modbus Master to Devices36 Siemens Energy & Automation, Inc.3. Select the device from the list by pressing Enteror the sp

Page 36 - 5.4 Device Setup—Port 2

5 Creating Project Files—Modbus Master to DevicesSiemens Energy & Automation, Inc. 37change the starting register to 10, the last registerwill

Page 37 - Modbus Master

5 Creating Project Files—Modbus Master to Devices38 Siemens Energy & Automation, Inc.4. Select a data register on the list and press Enter tosee a

Page 38 - Intermessage Time-Out

5 Creating Project Files—Modbus Master to DevicesSiemens Energy & Automation, Inc. 395. Select the data word (16 bit data) from the list andpre

Page 39 - 5.6 Device List Setup

5 Creating Project Files—Modbus Master to Devices40 Siemens Energy & Automation, Inc.3. Select a data item and press Enter to see a list ofdevice

Page 40

5 Creating Project Files—Modbus Master to DevicesSiemens Energy & Automation, Inc. 41To conserve registers when using VDEW devices, youshould s

Page 41

5 Creating Project Files—Modbus Master to Devices42 Siemens Energy & Automation, Inc.The relevant status codes (Text #) are listed below.Table 5.1

Page 42

5 Creating Project Files—Modbus Master to DevicesSiemens Energy & Automation, Inc. 43Once you are finished entering data, select Save tosave yo

Page 43

5 Creating Project Files—Modbus Master to Devices44 Siemens Energy & Automation, Inc.register 40001, etc. Be sure that the registers youspecified

Page 44

6 Creating Project Files—SEAbus Port ExpanderSiemens Energy & Automation, Inc. 456 Creating Project Files—SEAbus Port ExpanderThis chapter covers

Page 45

1 IntroductionSiemens Energy & Automation, Inc. 11Introduction1.1 Product OverviewThe Panel-Tec DTU3005 is an intelligent, multiple-function data

Page 46

6 Creating Project Files—SEAbus Port Expander46 Siemens Energy & Automation, Inc.6.1 Passthrough Setup—Port 1You must have a SEAbus Port Expander

Page 47 - 5.9 Global Command Registers

6 Creating Project Files—SEAbus Port ExpanderSiemens Energy & Automation, Inc. 47When 2-wire communications are being used, RTSmust be looped bac

Page 48 - 5.12 Saving the Project File

6 Creating Project Files—SEAbus Port Expander48 Siemens Energy & Automation, Inc.6.2 SEAbus Device Setup—Port 2One or more Siemens devices may be

Page 49 - Port Expander

7 Transferring Project FilesSiemens Energy & Automation, Inc. 497 Transferring Project FilesOnce you have configured and saved your project fil

Page 50 - 6.1 Passthrough Setup—Port 1

7 Transferring Project Files50 Siemens Energy & Automation, Inc..Figure 7.1 Null Modem Cable connectionThe null modem cable will cross pins 2 an

Page 51

1 Introduction2 Siemens Energy & Automation, Inc.1.4.1 PLC to SEAbusThe basic configuration is a PLC attached to port 1 ofthe DTU3005, and the S

Page 52 - 6.3 Passthrough Setup—Port 3

1 IntroductionSiemens Energy & Automation, Inc. 31.4.2 Modbus Master to SEAbusThe DTU3005 unit can be configured as a Modbus(RTU) slave. In this

Page 53 - 7 Transferring Project Files

1 Introduction4 Siemens Energy & Automation, Inc.Figure 1.7 Connection to Modbus Master using a Multidrop CableMulti-Drop Modbus Master to SEAbu

Page 54

1 IntroductionSiemens Energy & Automation, Inc. 51.4.3 SEAbus Port ExpanderThe DTU3005 can be used as a SEAbus port expanderfor ACCESS devices, a

Comments to this Manuals

No comments