Siemens Free Energy Band TH 193 HC User Manual Page 28

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 27
Thermostats
www.usa.siemens.com/hvaccomponents
A-28
Low Temp.
Part No. 134-1700
Ambient Temperature Range .............................Greater than setpoint to
140°F (60°C)
Pneumatic Switch ...........................NC, 0.020" (0.6 mm) diameter bleed
Control Point Low
Temperature Thermostat ..............................Lowest temperature at any
one foot section of the sensing bulb
Case Finish .............................................................. Gray Baked Enamel
Shipping Weight ............................................................2.45 lb. (1.11 kg)
Part No. 134-1710
Ambient Temperature Range .............................................-40 to +140°F
(-40 to +60°C)
Pneumatic Switch .............................NC, 0.02" (0.6 mm) diameter bleed
Control Point Low
Temperature Thermostat ..............................Lowest temperature at any
one foot section of the sensing bulb
Case Finish .............................................................. Gray Baked Enamel
Shipping Weight ........................................................... 2.38 lb. (1.08 kg)
Temperature Maximum Bulb Bulb & Capillary
Range Differential Temperature Length Switch Reclose Part No.
15 to 55°F 5°F (2.8°C) 400°F (204°C) 20' (6 m) Temperature must 134-1700
(-9 to +12.8°C) with Non-Adjustable increase by 5°F
stop at 35°F (1.67°C) (2.8°C) before
pneumatic switch can
be reclosed.
100 to 170°F 10°F (5.6°C) 250°F (121°C) 2.7" (69 mm) Dia. x Temperature must 134-1710
(38 to 77°C) Non-Adjustable 10" (25.4 cm) L bulb drop 10°F (5.6°C)
with 6' (183 mm) before pneumatic
capillary switch can be
reclosed.
134
High Temp.
Dimensions shown in inches (mm).
Dimensions
Specifi cations/Product Ordering
A-91
Accessories
& Service Kits
Page view 27
1 ... 27 28 29 30 31 32 33 34 35 36

Comments to this Manuals

No comments