Siemens SIMATIC NET User's Guide

Browse online or download User's Guide for Software Siemens SIMATIC NET. Siemens SIMATIC NET User`s guide User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - NET S7 I/O Server

Wonderware SiemensSIMATIC NET S7 I/O ServerUser’s GuideRevision FNovember 2000Wonderware Corporation

Page 2

6 Wonderware Siemens SIMATIC NET S7 I/O Server Configuring the I/O Server Once the server has been installed, some configuration is required. Configu

Page 3 - Contents

Configuring Automatic Topic Generation 7 Configuring Automatic Topic Generation The Automatic Topic Generation option is used to automatically generat

Page 4

8 Wonderware Siemens SIMATIC NET S7 I/O Server This option is selected when adding new names and is the safest (default) mode. It willnot change exi

Page 5 - NET S7 I/O Server

Configuring a Topic Definition 9 Configuring a Topic Definition Use the Topic Definition option from the Configure menu to create new, modify, ordelet

Page 6

10 Wonderware Siemens SIMATIC NET S7 I/O Server S7 Topic Definition Enter a unique name for the topic. Note When communicating with InTouch, this ex

Page 7

Configuring a Topic Definition 11 Select the name of the connection that will be used by this topic. Only connectionnames that correspond to the sel

Page 8 - View Menu

12 Wonderware Siemens SIMATIC NET S7 I/O Server With this 3 radio buttons you are able to tune the poking behaviour to the PLC. The 3modes behave as

Page 9 - File Menu

Configuring a Topic Definition 13 Timeouts are needed for block services to supervise the reading of initial values andupdating the block items to th

Page 10 - Configuring the I/O Server

14 Wonderware Siemens SIMATIC NET S7 I/O Server Configuring the I/O Server Settings Use the Server Settings option from the Configure menu to change t

Page 11 - Automatic Topic Generation

Configuring the I/O Server Settings 15 Enabling this option will cause the server to start as a Windows NT service. Windows NT offers the capability

Page 12

All rights reserved. No part of this documentation shall be reproduced, stored in aretrieval system, or transmitted by any means, electronic, mechani

Page 13 - Topic Definition

16 Wonderware Siemens SIMATIC NET S7 I/O Server Configuring Security Use the Security option from the configure menu to control server configurationch

Page 14 - S7 Topic Definition

Configuring Logger 17 Configuring Logger Use the Logger option from the configure menu to set the working logger mode of theserver. The options contr

Page 15

18 Wonderware Siemens SIMATIC NET S7 I/O Server Data Menu The Data menu contains two commands, Monitor and Dump Active Data, that areused for diagnost

Page 16

Data Menu 19 This drop down list box allows you to select any of the active topics. A preceding ‘*’indicates that at least one item in this topic ha

Page 17

20 Wonderware Siemens SIMATIC NET S7 I/O Server The item data list box displays information about each item. The box is divided into 6columns. The f

Page 18 - Server Settings

Data Menu 21 No access 0004 Bad, Configuration Error. Data communications are good. Data cannot be sentand/or received. Cannot access the item. The i

Page 19

22 Wonderware Siemens SIMATIC NET S7 I/O Server Click on an item line to open a dialog box displaying the item properties: Click OK to return to the

Page 20 - Configuring Security

Data Menu 23Dump Active Data Use the Dump Active Data option from the data menu to dump information on topicswith active items into an ASCII text file

Page 21 - Configuring Logger

24 Wonderware Siemens SIMATIC NET S7 I/O ServerDump Topic Database Use the DB Dump option from the data menu to dump the internal topic database into

Page 22 - Data Menu

Accessing I/O Server Help 25 Accessing I/O Server Help The Help menu contains two commands that are used to access help for the server. The following

Page 23

iContentsIntroduction ...1Communica

Page 24

26 Wonderware Siemens SIMATIC NET S7 I/O Server Item Names The Wonderware Siemens SIMATIC NET S7 IO Server uses an item namingconvention based on the

Page 25

Item Names 27Data Blocks DB (Datenbausteine)Instance Blocks DI (Instanzbausteine) Data Format Item/Point Suffix Data Type Range Bit D<B,I>d,X

Page 26

28 Wonderware Siemens SIMATIC NET S7 I/O Server Note All Data Blocks are Read/Write (d=1 to 65,535, x=0 to 65,535, n=0 to 65,534,m=0 to 65,532, y=0 t

Page 27 - Dump Active Data

Item Names 29Flag Bytes (Merker) (continued) Data Format Item/Point Suffix Data Type Range FINTn Integer -32768 to 32767 Integer MINTn In

Page 28 - Dump Topic Database

30 Wonderware Siemens SIMATIC NET S7 I/O Server Input Bytes (Eingänge) Data Format Item/Point Suffix Data Type Range Bit Ix.y Discrete 0 or 1

Page 29 - Accessing I/O Server Help

Item Names 31Input Bytes (Eingänge) (continued) Data Format Item/Point Suffix Data Type Range Double Word Array IDm,v EDm,v Message Message Hex

Page 30 - Item Names

32 Wonderware Siemens SIMATIC NET S7 I/O Server Output Bytes (Ausgänge) Data Format Item/Point Suffix Data Type Range Bit Ox.y Discrete 0 or 1

Page 31 - Item Names 27

Item Names 33Output Bytes (Ausgänge) (continued) Data Format Item/Point Suffix Data Type Range Double WordArray ODm,v ADm,v Message Message Hex

Page 32 - Flag Bytes (Merker)

34 Wonderware Siemens SIMATIC NET S7 I/O ServerPeripheral Input Bytes (Peripherieeingänge) (continued) Data Format Item/Point Suffix Data Type Ran

Page 33

Item Names 35Peripheral Input Bytes (Peripherieeingänge) (continued) Data Format Item/Point Suffix Data Type Range Real PIREALm PEREALm Real Rea

Page 34 - Input Bytes (Eingänge)

ii Table of ContentsItem Names ... 26

Page 35

36 Wonderware Siemens SIMATIC NET S7 I/O ServerPeripheral Output Bytes (Peripherieausgänge) (continued) Data Format Item/Point Suffix Data Type Ra

Page 36 - Output Bytes (Ausgänge)

Item Names 37Counters Data Format Item/Point Suffix Data Type Range Word Cx None Integer 0...65535 Zx None Integer 0 to 65535 BCD Intege

Page 37

38 Wonderware Siemens SIMATIC NET S7 I/O Server Block Items (continued) Data Format Item/Point Suffix Data Type Range Byte Array BLd,Bx,v Messag

Page 38 - (continued)

Item Names 39Alarms and EventsThe Wonderware Siemens SIMATIC NET S7 I/O Server offers the possibility to readAlarms and Events generated either by SFB

Page 39

40 Wonderware Siemens SIMATIC NET S7 I/O Server Alarms and Events (continued)Item Extension 1 Extension 2 Suffix Message RangeDINTm,vMessage Hex ASCII

Page 40

Item Names 41Note All Alarms and Events are Read only (<EV_ID> is the ID defined by Step7, ininteger format, filled with leading zeros up to 6

Page 41 - Block Items

42 Wonderware Siemens SIMATIC NET S7 I/O ServerPredefined Item/Point Names All S7 topics have predefined item/point names to monitor and control commu

Page 42 - Block Items (continued)

Predefined Item/Point Names 43 STORESETTINGS Item The STORESETTINGS item is used to make the temporary update interval changesvia I/O permanent. If t

Page 43 - Alarms and Events

44 Wonderware Siemens SIMATIC NET S7 I/O Server WRITECOMPLETE Item The WRITECOMPLETE item is used to access the state of pending write activities onth

Page 44

Predefined Item/Point Names 45READCOMPLETE ItemThe READCOMPLETE item is used to access the state of initial reads on all items inthe corresponding top

Page 45

Wonderware Siemens SIMATICNET S7 I/O ServerIntroductionThe Wonderware Siemens SIMATIC NET S7 I/O Server (referred to as the serverthrough the remain

Page 46 - Predefined Item/Point Names

46 Wonderware Siemens SIMATIC NET S7 I/O Server Monitoring the Status of Communications with a PLC For each topic name (PLC), there is a built-in disc

Page 47 - ERRORCOUNT Item

Reading Values from the I/O Server into Excel 47 Reading Values from the I/O Server into Excel Values may be read directly into Excel spreadsheets fro

Page 48 - STATUS Item

48 Wonderware Siemens SIMATIC NET S7 I/O Server Writing Values to the I/O Server from Excel Values may be written to the server from Microsoft Excel b

Page 49 - POLLNOW Item

Troubleshooting I/O Server Communication Problems 49 Troubleshooting I/O Server Communication Problems This section provides you with some simple step

Page 50

50 Wonderware Siemens SIMATIC NET S7 I/O Server The information in the second line indicates that you have at least one I/O typetagname defined in you

Page 51

Troubleshooting I/O Server Communication Problems 515. If the topic name is different, either correct it in the server or switch toWindowMaker and co

Page 52

52 Wonderware Siemens SIMATIC NET S7 I/O ServerDebugging Communication Between an I/O Serverand a PLCThis section provides you with simple steps to di

Page 53

Troubleshooting I/O Server Communication Problems 538 Also, if you are using an AT type computer, two devices cannot shareinterrupts. Verify that the

Page 54

54 Wonderware Siemens SIMATIC NET S7 I/O Server2. If you are running Windows for Workgroups (version 3.1 or later), downloadSERIAL.386 (this fixes a

Page 55

Troubleshooting I/O Server Communication Problems 55Ø If you are using the Windows 95 operating system, verify the following:1. Click Start on the Wi

Page 56

2 Wonderware Siemens SIMATIC NET S7 I/O ServerSuiteLink uses a TCP/IP based protocol and is designed specifically to meet industrialneeds such as data

Page 57

56 Wonderware Siemens SIMATIC NET S7 I/O Server4. Click Advanced. The Advanced Port Settings dialog box appears:5. Lowering the default Receive Buf

Page 58

Troubleshooting I/O Server Communication Problems 57Ø How long is your RS-232 cable? Fifteen meters (fifty feet) is the maximum practical length for

Page 59

58 Wonderware Siemens SIMATIC NET S7 I/O ServerØ Increase the Reply Timeout setting in the I/O Server to a value between 5 and 10seconds.Not allowing

Page 60

Troubleshooting I/O Server Communication Problems 592. The computer can not use an OEM (Original Equipment Manufacturer) version ofMicrosoft Windows.

Page 61

60 Wonderware Siemens SIMATIC NET S7 I/O Server Special Wonderware Logger Messages The following messages may appear in the Wonderware Logger. They c

Page 62

Special Wonderware Logger Messages 61 Your configured CP/VFD couldn’t be initialised. Goto “Setting the PG-PC interface”for diagnostics.• ERROR(<e

Page 63

62 Wonderware Siemens SIMATIC NET S7 I/O Server• Write complete (OK) - item: <item name> on: <topic name> The write operation was compl

Page 64

Special Wonderware Logger Messages 63For example:PROTOCOL: s7_get_cycl_read_ind dumping read valuesDB222,B0,6: result=255, value=0x000000000000, var_l

Page 65

64 Wonderware Siemens SIMATIC NET S7 I/O Server

Page 66

Getting Started Quickly with the I/O Server 3 Getting Started Quickly with the I/O Server This section briefly describes the components and procedures

Page 67

4 Wonderware Siemens SIMATIC NET S7 I/O Server S7 Main Window When the server starts, the main window will appear: The current configuration file and

Page 68

File Menu 5File MenuFile menu options deal with loading and saving the internal topic configuration database. New Clears the internal topic database f