P/N 315-049403-1 Siemens Building TechnologiesFire SafetyFireSeekerFire Alarm Control PanelModel FS-250Programming Manual

Page 2

FS-250 PROGRAMMING MANUAL14User LevelPressing the menu button displays the User level functions. The user menu allowsthe operator to activate General

Page 3 - Table Of Contents

FS-250 PROGRAMMING MANUAL15Activating a RecallIt is possible to sound a Recall from the keypad using the following stepsPress “Menu” Press “Recall” Di

Page 4

FS-250 PROGRAMMING MANUAL17Maintenance LevelFollowing are the details of the Maintenance level functionsEnabling/Disabling DevicesThe disable / enable

Page 5 - The Access levels

FS-250 PROGRAMMING MANUAL18Enabling/Disabling NACsThe Notification Appliance Circuits may be disabled/enabled as follows:Press“Disable/Enable”Press “O

Page 6 - Technician Level

FS-250 PROGRAMMING MANUAL19Changing the Maintenance PasswordThe password for access to the Maintenance level menus may be changed asfollows from the M

Page 7 - The Operator Interface

FS-250 PROGRAMMING MANUAL20Clearing the historyThe panel can store the last 2000 events in the event history. The informationdisplayed includes the da

Page 8

FS-250 PROGRAMMING MANUAL21Starting Quick TestThe Quick Test mode allows quick and easy testing of the installation. It will allowthe devices to be a

Page 9

FS-250 PROGRAMMING MANUAL31APPENDIX A: GLOSSARYAlarm Signal. A signal indicating an emergency requiring immediate action, such asan alarm for fire fro

Page 10 - User Level

FS-250 PROGRAMMING MANUAL32FACP. Fire Alarm Control PanelGeneral Alarm. A term usually applied to the simultaneous operation of all thenotification ap

Page 11 - Viewing the event history

FS-250 PROGRAMMING MANUAL33Output Zone. There may be 255 output zones. Normally used to specify an area ofthe building for signaling. The output devi

Page 13 - Enabling/Disabling NACs

FS-250 PROGRAMMING MANUAL34APPENDIX B: REFERENCES• NFPA 72: National Fire Alarm Code (National Fire Protection Association)• NFPA 70: National Elect

Page 14 - FS-250 PROGRAMMING MANUAL

Table Of ContentsIntroduction...1The Access levels

Page 15

Setting the Date Format...19Clearing the history...

Page 16 - Programming a device

FS-250 PROGRAMMING MANUAL1IntroductionThe FS-250 Fire Alarm Control Panels are completely field programmable. Althoughprogramming requires no special

Page 17 - APPENDIX A: GLOSSARY

FS-250 PROGRAMMING MANUAL2Maintenance LevelThe Maintenance level is accessed via the User Menu and the correct password.The functions accessible in th

Page 18

FS-250 PROGRAMMING MANUAL3The Operator InterfaceInterface for User and Maintenance LevelsThe operator interface for configuring and programming the FS

Page 19

FS-250 PROGRAMMING MANUAL4Interface for the Technician LevelWhen the Technician Level is accessed using the password, the LCD display andthe keypad ar

Page 20 - APPENDIX B: REFERENCES

FS-250 PROGRAMMING MANUAL5Entering Alphanumeric CharactersEntry of alphanumeric data using keypad is as follows:• Each character is entered using a t