Siemens Server User Manual Page 9

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 8
Overview of ChemWeb Server
3
Ext. Reset
If the reset input is connected more than 3 seconds to ground GND or the RESET key is pressed at
least 3 seconds, a reset is carried out at the webserver as well as at the modem module.
Terminal No.: Designation: Explanation:
5 GND Ground
6 Reset Input for external reset of ChemWeb Server
Inputs (IN1, IN2)
The two digital inputs are fitted internally with pull-up resistors and are activated by connecting them
to GND. On activation, digital input 1 (IN1) dials into the internet via the set parameters. Digital input
2 (IN2) deactivates the installed modem to enable null modem operation via COM 1.
Terminal No.: Designation: Explanation:
7 GND Ground
8 IN1 Digital input 1 – Dialing into internet
9 IN2 Digital input 2 – Switching over to null modem operation
10 GND Ground
COM 0 - W&T RS485 bus (W&T - RS232)
The serial interface is activated as RS485 port by setting a coding jumper (RS485 enable – GND). At
the same time the RS232 interface via DSUB plug is switched off. Without the coding jumper this
interface works as standard RS232 via the DSUB connection.
This DSUB connection must not be used in the case of RS485
operation!
Double data lines A and B are connected to the terminals so that the internally existent pull-up, pull-
down and bus terminating resistors can easily be wired externally, if required.
If the ChemWeb Server is located at an end position of the RS485 bus, the terminating resistor
“Termination” (11) has to be connected to A (15). If the device is coupled in the bus center,
“Termination” must remain open.
At least at one point of the bus, the data lines should be connected to B by means of resistor Symm
(+) and to A by means of resistor Symm (-) in order to avoid floating of the data lines.
Terminal No.: Designation: Description:
MG/L 5
Connection
11 Termination Bus terminating resistor (at end of RS485 bus) -------
12 Symm (-) Balancing resistor 1 (1 x in RS485 bus) -------
13 Symm (+) Balancing resistor 2 (1 x in RS485 bus) -------
14 B Data line B -------
15 A Data line A -------
16 B Data line B Terminal 20
17 A Data line A Terminal 21
18 RS485 enable Switchover RS485 - RS232 -------
19 GND Ground -------
Page view 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 47 48

Comments to this Manuals

No comments