Siemens Industrial Ethernet Switches SCALANCE X-200 User Manual Page 116

  • Download
  • Add to my manuals
  • Print
  • Page
    / 296
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 115
Product properties
3.26 C-PLUG (configuration plug)
SCALANCE X-200
116 Operating Instructions, 12/2011, A5E00349864-19
3.26 C-PLUG (configuration plug)
Area of application
The C-PLUG is an exchangeable medium for storage of the configuration and project
engineering data of the basic device. This means that the configuration data remains
available if the basic device is replaced.
How it works
Power is supplied by the basic device. The C-PLUG retains all data permanently when the
power is turned off.
If an empty C-PLUG (factory settings) is inserted, all configuration data of an IE
Switch X-200 is saved to it when the device starts up. Changes to the configuration during
operation are also saved on the C-PLUG without any operator intervention being necessary.
If a C-PLUG is inserted, the configuration stored internally on the basic device is no longer
changed. Al changes made to the configuration during ongoing operation are only stored on
the C-PLUG.
A basic device with an inserted C-PLUG automatically uses the configuration data of the
C-PLUG when it starts up. This is, however, only possible when the data was written by a
compatible device type.
This allows fast and simple replacement of the basic device. If a device is replaced, the C-
PLUG is taken from the failed component and inserted in the replacement device. The first
time it is started up, the replacement device has the same configuration as the failed device
except for the MAC address set by the vendor.
Compatible devices
As a general rule, the data on the C-PLUG is only compatible with devices having an
identical order number and the same device name.
The device combinations shown in the following table are exceptions. With these devices,
the exchange of the C-PLUG is possible in one direction.
Table 3- 25 Device combinations between which the C-PLUG can be exchanged:
Device type
SCALANCE
C-PLUG created by device with
order number
Compatible with device with
order number
X208 6GK5208-0BA00-2AA3 6GK5208-0BA10-2AA3
X204-2 6GK5204-2BB00-2AA3 6GK5204-2BB10-2AA3
X206-1 6GK5206-1BB00-2AA3 6GK5206-1BB10-2AA3
X204-1LD 6GK5204-2BC00-2AA3 6GK5204-2BC10-2AA3
6GK5206-1BC10-2AA3 X206-1LD 6GK5206-1BC00-2AA3